Physical Data
The Flooding Charges listed in the table above
reflect additional refrigerant required for split
condenser method of winter control above normal
summer operating charge and heat reclaim coil
requirements.
Note:
Condenser ambient should be noted when
determining the flooding charge.
• If above 65ÞF, add the specified amounts of
refrigerant when the system stabilizes after
start-up.
• If below 65ÞF but above the coldest expected,
some condenser flooding will already be occur-
ring and required additional charge will be
lower.
• If the coldest expected temperature is above
20ÞF, the flooding charge required will be less
than 50% of each condenser circuit.
REMOTE SATELLITES & CONDENSERS
September 1, 1997
5 - 6
HUSSM ANN CORPORATION • BRIDGETON, M O 63044-2483 • Printed in USA
Table 5-1 — Physical Data
Weight /w
Max Flood
Inlet/Outlet
No.
FLA 3PH
Max. Flood
Charge
Connections
Model
Fans
(lbs)
(lbs)
OD
R404A/
R404A/
208V 230V 460V
R22
R507
R22
R507
1x1
2.8
2.6
1.3
205
221
19
35
1
1/8
HLCV
B
1x2
5.6
5.2
2.6
410
445
40
75
1
3/8
*
1x3
8.4
7.8
3.9
615
666
59
110
1
3/8
1x4
11.2
10.4
5.2
925
1002
88
165
1
5/8
1x5
14.0
13.0
6.5
1039
1125
99
185
2
1/8
1x6
16.8
15.6
7.8
1239
1343
119
223
2
1/8
1x7
19.6
18.2
9.1
1551
1679
147
275
2
5/8
1x2
8.8
8.0
4.0
1081
1137
64
120
1
5/8
HLCV
F
1x3
13.2
12.0
6.0
1574
1658
96
180
2
1/8
1x4
17.6
16.0
8.0
2240
2352
128
240
1
5/8
HLCV
G
1x5
22.0
20.0
10.0
3020
3231
242
453
2
5/8
1x6
26.4
24.0
12.0
3555
3809
291
545
2
5/8
2x2
11.2
10.4
5.2
820
897
88
165
1
3/8
*
HLCV
I
2x3
16.8
15.6
7.8
1230
1334
119
223
1
3/8
2x4
22.4
20.8
10.4
1850
2003
176
329
1
5/8
2x5
28.0
26.0
13.0
2078
2263
212
397
2
1/8
2x6
33.6
31.2
15.6
2420
2627
237
444
2
1/8
2x7
39.2
36.4
18.2
3075
3332
295
552
2
5/8
2x2
17.6
16.0
8.0
2001
2113
128
240
1
5/8
HLCV
V
2x3
26.4
24.0
12.0
2889
3055
191
357
2
1/8
2x4
35.2
32.0
16.0
3733
3955
255
477
2
1/8
HLCV
W
2x5
44.0
40.0
20.0
5020
5433
474
887
2
5/8
2x6
52.8
48.0
24.0
6030
6527
570
1067
2
5/8
*Inlet = 1
3/8
, Outlet = 1
1/8
O
N
E
F
A
N
W
I
D
E
T
W
O
F
A
N
S
W
I
D
E
Return to Contents