3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
60
Figure 3-38
Cables routed outside the cabinet
The T/H sensors inside the cabinet are secured at the return air side and their IN ports are connected
to the main control board. When connecting the T/H sensors outside the cabinet, connect the OUT
port of one T/H sensor inside the cabinet to the IN port of the next T/H sensor outside the cabinet.
Connect all T/H sensors in series in this way.
The T/H sensors should be 1.5 m above the ground (33 U).
Each smart cooling product supports a maximum of ten T/H sensors.
Step 2
shows how to set the DIP switches for T/H sensors.
Figure 3-39
DIP switches
Table 3-5
DIP switch setting on a T/H sensor
Position
Name
Address DIP Switch ID
1
2
3
4
5
6
Return air
Return air 2
temp/humid
1
ON
OFF
OFF
OFF
OFF
OFF
Cold aisle
Cold aisle 1
11
ON
ON
OFF
ON
OFF
OFF