NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
121
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Cause
Solution
3. A slave unit is
offline.
unit to the actual
number of units.
3. Check the
teamwork cable
connection and
running status of the
slave units.
a118
Main power
failure alarm
Major
Generates an
alarm
1. The primary power
supply is faulty.
2. The cables to the
primary power supply
are loose or damaged.
1. Check the primary
power supply.
2. Check the cables to
the primary power
supply.
a130
Water inlet
solenoid valve
fault alarm
Major
Generates an
alarm and shuts
down the
humidifier.
1. The cables to the
water inlet solenoid
valve are loose or
damaged.
2. The water inlet
solenoid valve is faulty.
1. Check the cables to
the water inlet
solenoid valve.
2. Replace the water
inlet solenoid valve.
a179
Humidifier
pump
abnormal
alarm
Major
Generates an
alarm and shuts
down the
humidifier.
1. The water pump inlet
is blocked.
2. The cables to the
water pump are loose
or damaged.
3. The water pump is
faulty.
4. The water pump
races due to a liquid
level detection fault.
5. The water pump is
blocked.
1. Clear the blockage
from the water pump
inlet.
2. Verify that the
water pump cables are
properly connected.
3. Replace the water
pump.
4. Rectify the liquid
level detection fault.
5. Replace the water
pump.
a180
Humidifier wet
film
replacement
due-in alarm
Warning
Generates an
alarm
The accumulated
runtime of the wet film
of the humidifier
exceeds the alarm
threshold.
Maintain or replace
the wet film of the
humidifier and clear
the accumulated
runtime.
a181
Humidifier
pump exceed
runtime alarm
Warning
Generates an
alarm
The accumulated
runtime of the water
pump exceeds the
alarm threshold.
Maintain or replace
the water pump and
clear the accumulated
runtime.
a182
Water supply
abnormal
alarm
Major
Generates an
alarm and shuts
down the
humidifier.
1. The water supply is
insufficient.
2. The humidifier float
has dropped and is
jammed.
3. The humidifier float
1. Verify that water
supply to the
humidifier is normal.
2. Verify that the
humidifier float can
float and drop