NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
153
Alarm
ID
Alarm
Name
Alarm
Severit
y
Impact Possible Cause
Solution
three-phase
detection board
is faulty.
working range.
2.
Replace the SPD
three-phase
detection board.
A280-02
Power
frequency
abnormal
Major
An
alarm is
triggere
d.
1.
The power
supply frequency
exceeds the
upper threshold.
2.
The SPD
three-phase
detection board
is faulty.
1.
Check the power
supply
frequency, and
ensure that it is
within the
working range.
2.
Replace the
SPD three-phase
detection board.
A281-01
Power
voltage
abnormal
Major
An
alarm is
triggere
d, and
the
smart
cooling
product
is shut
down.
The input voltage is
below the lower
threshold.
Check the power
supply voltage.
A281-02
Power
voltage
abnormal
Major
An
alarm is
triggere
d, and
the
smart
cooling
product
is shut
down.
The input voltage
exceeds the upper
threshold.
Check the power
supply voltage.
6.3 Troubleshooting
describes the common faults of the NetCol5000-C and handling methods.
Table 6-4
Common faults of the NetCol5000-C and handling methods
Symptom
Possible Causes
Troubleshooting
The fan does not
rotate after the
NetCol5000-C
1.
The power supply
module of the fan is
faulty or abnormal
1.
Ensure that the power supply
module of the fan is inserted to
the subrack. If the fault persists,