3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
38
Figure 3-13
Removing an air filter
Step 3
Take out the desiccant bag.
Step 4
Press and hold the manual adjustment switch and manually turn the chilled water valve to the
100% state, as shown in
Figure 3-14
Adjusting the chilled water valve
Step 5
Use a screwdriver to open the exhaust valve shown in
the hose.