NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
136
Alarm
ID
Alarm
Name
Alarm
Severit
y
Impact Possible Cause
Solution
interrupt
alarm
d.
PSU are loose or
damaged.
2.
The PSU is
faulty.
3.
The
communications
port of the main
control board is
faulty.
PSU.
2.
Maintain or
replace the PSU.
3.
Maintain or
replace the main
control board.
A077-01
Indoor fan
1 fault
Major
An
alarm is
triggere
d.
1.
The power
supply to the
indoor fan is
abnormal.
2.
The cables to the
indoor fan are
loose or
damaged.
3.
The indoor fan is
faulty.
1.
Check the power
supply to the
indoor fan.
2.
Check the cables
to the indoor fan.
3.
Maintain or
replace the
indoor fan.
Indoor fan
2 fault
Major
An
alarm is
triggere
d.
1.
The power
supply to the
indoor fan is
abnormal.
2.
The cables to the
indoor fan are
loose or
damaged.
3.
The indoor fan is
faulty.
1.
Check the power
supply to the
indoor fan.
2.
Check the cables
to the indoor fan.
3.
Maintain or
replace the
indoor fan.
Indoor fan
3 fault
Major
An
alarm is
triggere
d.
1.
The power
supply to the
indoor fan is
abnormal.
2.
The cables to the
indoor fan are
loose or
damaged.
3.
The indoor fan is
faulty.
1.
Check the power
supply to the
indoor fan.
2.
Check the cables
to the indoor fan.
3.
Maintain or
replace the
indoor fan.
Indoor fan
4 fault
Major
An
alarm is
triggere
d.
1.
The power
supply to the
indoor fan is
abnormal.
2.
The cables to the
indoor fan are
loose or
damaged.
3.
The indoor fan is
1.
Check the power
supply to the
indoor fan.
2.
Check the cables
to the indoor fan.
3.
Maintain or
replace the
indoor fan.