6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
134
Alarm
ID
Alarm
Name
Alarm
Severit
y
Impact Possible Cause
Solution
temperatur
e alarm
triggere
d.
temperature and
humidity sensors
are located in
inappropriate
positions.
2.
The thermal load
power is high or
the cooling
capacity is
insufficient.
3.
The ambient
temperature
exceeds the
upper threshold.
4.
The high
temperature
alarm threshold
is inappropriate.
5.
The value
detected by the
temperature
sensor or
temperature and
humidity sensor
is different from
the actual value.
6.
The chilled water
flow is
insufficient, or
the supply water
temperature is
high.
7.
The chilled water
valve is stuck or
faulty.
temperature
sensors or
temperature and
humidity
sensors.
2.
Add smart
cooling products
or contact
Huawei technical
support.
3.
Measure the
ambient
temperature.
Check whether
other causes
exist if the alarm
persists in a long
time after
startup.
4.
Adjust the high
temperature
alarm threshold.
5.
Calibrate or
replace the
temperature
sensor or
temperature and
humidity sensor.
6.
Check the
pressure and
temperature of
chilled water.
7.
Maintain or
replace the
chilled water
valve.
A051-01
Hot aisle
high
temperatur
e alarm
Critical
An
alarm is
triggere
d.
1.
The temperature
sensors or
temperature and
humidity sensors
are located in
inappropriate
positions.
2.
The thermal load
power is high or
the cooling
capacity is
insufficient.
3.
The ambient
1.
Adjust the
positions of the
temperature
sensors or
temperature and
humidity
sensors.
2.
Add smart
cooling products
or contact
Huawei technical
support.
3.
Measure the