NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
3 Installation
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
47
Ensure that pipes and power cables are routed through separate holes.
Do not prepare extra knock-out holes to avoid performance loss.
Step 3
Remove the water pipe plug using an open-end wrench.
Step 4
Apply screw thread sealant evenly on the connecting position of external screw threads at
pipe ends, and install the pipes from inside out.
Step 5
Use a common wrench (open end: 53 mm) and trimo wrench (18#) to connect and secure
water inlet and outlet pipes.
Step 6
Attach thermal insulation foam to the pipes and ensure that the foam is in close contact with
the pipes.
Step 7
After pipes are connected, seal the gaps between the knock-out holes and the pipes using
sealant or foaming agent.
Figure 3-24
Connecting the water inlet and outlet pipes
----End
3.8.4.2 Connecting Aluminum Plastic Pipes
Procedure
Step 1
Open the rear door and remove the air filter.
Step 2
Knock off the knock-out holes for the chilled water inlet and outlet pipes.