NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
135
Alarm
ID
Alarm
Name
Alarm
Severit
y
Impact Possible Cause
Solution
temperature
exceeds the
upper threshold.
4.
The high
temperature
alarm threshold
is inappropriate.
5.
The value
detected by the
temperature
sensor or
temperature and
humidity sensor
is different from
the actual value.
6.
The chilled water
flow is
insufficient, or
the supply water
temperature is
high.
7.
The chilled water
valve is stuck or
faulty.
ambient
temperature.
Check whether
other causes
exist if the alarm
persists in a long
time after
startup.
4.
Adjust the high
temperature
alarm threshold.
5.
Calibrate or
replace the
temperature
sensor or
temperature and
humidity sensor.
6.
Check the
pressure and
temperature of
chilled water.
7.
Maintain or
replace the
chilled water
valve.
A053-01
PSU 1
fault alarm
Major
An
alarm is
triggere
d.
The PSU is faulty.
Maintain or replace
the PSU.
PSU 2
fault alarm
Major
An
alarm is
triggere
d.
The PSU is faulty.
Maintain or replace
the PSU.
A054-01
PSU 1
communic
ation
interrupt
alarm
Major
An
alarm is
triggere
d.
1.
The
communications
cables of the
PSU are loose or
damaged.
2.
The PSU is
faulty.
3.
The
communications
port of the main
control board is
faulty.
1.
Check the
communications
cables of the
PSU.
2.
Maintain or
replace the PSU.
3.
Maintain or
replace the main
control board.
PSU 2
communic
ation
Major
An
alarm is
triggere
1.
The
communications
cables of the
1.
Check the
communications
cables of the