NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
132
Alarm
ID
Alarm
Name
Alarm
Severit
y
Impact Possible Cause
Solution
alarm
A042-01
Remote
shutdown
alarm
Major
An
alarm is
triggere
d, and
the
smart
cooling
product
is shut
down.
1.
The remote
shutdown dry
contact is
triggered.
2.
The cables to the
remote shutdown
dry contact are
loose or
damaged.
1.
Check the status
of the remote
shutdown dry
contact.
2.
Check the cables
to the remote
shutdown dry
contact.
A044-01
Smoke
sensor
alarm
Critical
An
alarm is
triggere
d, and
the
smart
cooling
product
is shut
down.
1.
Smoke is
generated in the
equipment room.
2.
The cables to the
smoke sensor are
loose or
damaged.
3.
The smoke
sensor is faulty.
1.
Expel smoke
from the
equipment room
and reset the
smoke sensor.
2.
Check the cables
to the smoke
sensor.
3.
Maintain or
replace the
smoke sensor.
A048-01
Supply air
high
temperatur
e alarm
Critical
An
alarm is
triggere
d.
1.
The temperature
sensors or
temperature and
humidity sensors
are located in
inappropriate
positions.
2.
The thermal load
power is high or
the cooling
capacity is
insufficient.
3.
The ambient
temperature
exceeds the
upper threshold.
4.
The high
temperature
alarm threshold
is inappropriate.
5.
The value
detected by the
temperature
sensor or
temperature and
humidity sensor
1.
Adjust the
positions of the
temperature
sensors or
temperature and
humidity
sensors.
2.
Add smart
cooling products
or contact
Huawei technical
support.
3.
Measure the
ambient
temperature.
Check whether
other causes
exist if the alarm
persists in a long
time after
startup.
4.
Adjust the high
temperature
alarm threshold.
5.
Calibrate or
replace the