NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
115
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Cause
Solution
module.
a077
Indoor fan fault
alarm
Major
Generates an
alarm
1. The power supply to
the indoor fan is
abnormal.
2. The cables to the
indoor fan are loose or
damaged.
3. The indoor fan is
faulty.
1. Check the power
supply to the indoor
fan.
2. Check the cables to
the indoor fan.
3. Maintain or replace
the indoor fan.
a079
Drain
abnormal
alarm
Major
Generates an
alarm and shuts
down the
humidifier.
1. The drainage filter is
blocked.
2. The drainpipe is
blocked.
3. (Optional) The
condensate water pump
is faulty.
4. The low liquid level
sensor is faulty.
1. Clear the foreign
matter in the water
pan and filter.
2. Check that the
drainpipe is not
blocked or bent.
3. (Optional) Check
the cables to the
condensate water
pump, clear the
foreign matter in the
water pump, or
replace the pump.
4. Check the cables to
the low liquid level
sensor, clear the
obstacles, or replace
the low liquid level
sensor.
a080
Chilled water
valve exceed
runtime alarm
Warning
Generates an
alarm
The accumulated
runtime of the chilled
water valve exceeds the
alarm threshold.
Maintain or replace
the chilled water valve
and clear the
accumulated runtime.
a081
Power 1 input
overvoltage
alarm
Major
Generates an
alarm and shuts
down the smart
cooling product
system.
The input voltage
exceeds the upper
threshold.
Check the power
supply voltage.
a082
Power 1 input
undervoltage
alarm
Major
Generates an
alarm and shuts
down the smart
cooling product
system.
The input voltage is
below the lower
threshold.
Check the power
supply voltage.
a090
(Optional)
Condensate
pump exceed
runtime alarm
Warning
Generates an
alarm
The water pump
runtime exceeds the
threshold.
Maintain or replace
the water pump and
clear the accumulated
runtime.