NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
117
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Cause
Solution
valve.
a093
High humidity
alarm
Warning
Generates an
alarm
1. The thermal load
power is low.
2. The ambient
humidity exceeds the
upper threshold.
3. The temperature and
humidity sensor is not
installed in a proper
position.
4. The high humidity
alarm threshold is
inappropriate.
5. The value detected
by the temperature and
humidity sensor is
different from the
actual value.
1. Contact Huawei
technical support.
2. Measure the
ambient humidity.
3. Adjust the position
of the temperature and
humidity sensor.
4. Adjust the high
humidity alarm
threshold.
5. Calibrate or replace
the temperature and
humidity sensors.
a094
Low humidity
alarm
Warning
Generates an
alarm
1. The ambient
humidity is below the
lower threshold.
2. The temperature and
humidity sensor is not
installed in a proper
position.
3. The low humidity
alarm threshold is
inappropriate.
4. The value detected
by the temperature and
humidity sensor is
different from the
actual value.
1. Measure the
ambient humidity.
2. Adjust the position
of the temperature and
humidity sensor.
3. Adjust the low
humidity alarm
threshold.
4. Calibrate or replace
the temperature and
humidity sensors.
a096
Supply-water
temperature
invalid
Major
Generates an
alarm
1. The cables to the
temperature sensor are
loose or damaged.
2. The temperature
sensor is faulty.
1. Check the cables to
the temperature
sensor.
2. Maintain or replace
the temperature
sensor.
a097
Supply-water
high
temperature
alarm
Major
Generates an
alarm
1. The temperature of
chilled water is higher
than the supply water
high temperature alarm
threshold.
2. The supply water
high temperature alarm
1. Check the
temperature of
supplied chilled water.
2. Adjust the supply
water high
temperature alarm
threshold.