NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 07 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
118
Alarm
ID
Alarm Name
Alarm
Severity
Impact
Possible Cause
Solution
threshold is
inappropriate.
3. The supply and
return water pipes are
reversely installed.
4. The supply and
return water sensors are
reversely installed.
5. The supply water
temperature displayed
is different from the
actual temperature.
3. Exchange the
positions of the supply
and return water
pipes.
4. Exchange the
positions of the supply
and return water
sensors.
5. Calibrate or replace
the supply water
temperature sensor.
a098
Supply-water
low
temperature
alarm
Warning
Generates an
alarm
1. The temperature of
chilled water is lower
than the supply water
low temperature alarm
threshold.
2. The supply water
low temperature alarm
threshold is
inappropriate.
3. The supply water
temperature displayed
is different from the
actual temperature.
1. Check the
temperature of
supplied chilled water.
2. Adjust the supply
water low temperature
alarm threshold.
3. Calibrate or replace
the supply water
temperature sensor.
a099
Return-water
temperature
invalid
Major
Generates an
alarm
1. The cables to the
temperature sensor are
loose or damaged.
2. The temperature
sensor is faulty.
1. Check the cables to
the temperature
sensor.
2. Maintain or replace
the temperature
sensor.
a101
Chilled water
valve feedback
abnormal
alarm
Warning
Generates an
alarm
1. The cables to the
chilled water valve are
loose or damaged.
2. The chilled water
valve is faulty.
1. Check the control
cable connection to
the chilled water
valve.
2. Maintain or replace
the chilled water
valve.
a102
Indoor fan
overspeed
alarm
Major
Generates an
alarm
1. The cables to the
indoor fan are loose or
damaged.
2. The indoor fan is
faulty.
1. Check the cables to
the indoor fan.
2. Maintain or replace
the indoor fan.
a104
In-cabinet
water overflow
alarm
Critical
Generates an
alarm and shuts
down the smart
1. The water overflow
sensor detects water or
the sensor is faulty.
1. While configuring
the water overflow
sensor, check and