2 Installing Cabinets
Issue 02 (2015-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
17
Figure 2-15
Adjusting the height of the leveling base anchors (unit: mm)
3.
Install two adaptive bars into the side without side panels so that the total width of the
adaptive frame is 200 mm, and use M5 self-tapping screws to secure the adaptive bars.
Figure 2-16
Installing adaptive bars
4.
Lift the adaptive frame, and adjust its position so that its side without side panels is
closely attached to the 1200 mm deep cabinet.
5.
Adjust the leveling base anchors so that the left cabinets are at the same height.
6.
Use connecting plates to combine the adaptive frame with the cabinet. Use an 86 mm