A.1 Combining Liebert APM UPS Cabinets
Procedure
Step 1
Remove top panels from the two server cabinets adjacent to the UPS, as shown in
Figure A-1
Removing top covers
You are advised to work with another person when removing a top cover, top covers must be
installed back with the front and back directions matched exactly as before they are removed (the
end with a latch is at the top of the rear door).
When removing a top cover, open the latch at the top of the rear cabinet door (as shown in step 1 in
the
), and then push the top cover upwards until it is separate from the rear door frame.
Slightly pull the top cover backward. After the part shown in step 2 in
the rack, remove the top cover.
Step 2
Put a combining bar on the UPS sealing support, and screw it into the cabinet by using M5x10
tapping screws, as shown in