IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
10 Cable Layout
Issue 02 (2015-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
179
Component
Configuration
Configuration Number
V-100 Ah Battery
Battery tray
Battery tray for 4 batteries
10 PCS
Circuit breaker
Circuit breaker,
Pyromagnetic Breaker, 380
V AC/500 V DC, 160 A, 4P,
36 kA, 102 (W)*70 (D)*130
(H)
1 PCS
Battery cable
Battery Accessory, SD-480
V 100 Ah/12 V-PX-25 (ET),
Cables for battery group
SHOTO 6-GFM-100
embedded in battery cabinet
of IDC (25 mm
2
), IDC
special
1 PCS
Figure 10-33
Conceptual diagram of battery cable connections
Configuration 9
Configuration 9 applies to the scenario where the actual total power is greater than 8 kW but
no greater than 12 kW, and the backup time is 30 minutes. The following table describes
battery cabinet configuration.