IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
10 Cable Layout
Issue 02 (2015-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
229
Figure 10-60
Connecting monitoring cables to a lighting control box
Table 10-65
Cable connections for a lighting control box
Item
Port
Function
(1)
24V DC OUTPUT
Connects to the light in a
cabinet.
(2)
C SW1 and C SW2
Connects to the light switch
in an aisle.
(3)
C INFARA1 to C INFARA4 Connects to the signal cable
for the infrared sensor
switch (polarity insensitive).
(4)
INFRA POWER
Connects to the power cable
for the infrared sensor
switch (polarity sensitive),
with the brown wire
connecting to pole L and
blue wire to pole N.
(5)
LAMP OUTPUT
Connects to the power cable
for the light in an aisle, with
the brown wire connecting
to pole L and blue wire to
pole N.
----End
10.12.24 (Optional) Connecting a Monitoring Cable to an NVR
Prerequisites
A network cable used for monitoring has been prepared.
Procedure
Step 1
Connect one end of the network cable to the Ethernet port on the NVR, as shown in