IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
10 Cable Layout
Issue 02 (2015-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
156
Figure 10-6
Cable connections
(1) Double door electromagnetic lock
(2) Wire harness A
(3) Four-core cable A
(4) Wire harness B
(5) Four-core cable B
(6) Rear of the emergency door release button
Secure wire harness A near the magnetic locks using a cable tie.
2.
Strip four-core cable A delivered with the cabinet and connect it to the other end of wire
harness A. Then route the cables to the emergency door release button according to
shows the cable connections.
3.
Directly connect the yellow cable to binding post 2 at the rear of the emergency door
release button and the other three to wire harness B delivered with the cabinet.
4.
Strip four-core cable B delivered with the cabinet and connect the yellow cable to
binding post 1 at the rear of the emergency door release button and the other three to the
other end of wire harness B.
After connecting cables to wire harness B, place wire harness B near the emergency door release button
without securing it.
5.
Route four-core cable B out of the aisle and finally to the access control controller in the
cabling cabinet according to