FusionModule5000 Smart Modular Data Center
Commissioning Guide
5 Commissioning the Cooling System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
39
Parameter
Description
Configuration
Principle
Default
Value
Cascade
function
After the requirement
control is enabled, you
can configure
Cascade
function
. The cascade
function starts standby
smart cooling products if
the active one cannot
meet the refrigerating
requirements.
If the heat load to the
device increases, the
cascade function is
recommended.
Disable
Step 3
Complete the teamwork settings for all the smart cooling products by performing
Step 4
On the home screen of any teamwork controlled smart cooling product, tap
. If the
teamwork control succeeds, the teamwork topology of the smart cooling product in the group
is displayed, as shown in
describes the note for the screen.
Figure 5-6
Teamwork topology
Table 5-6
Notes for the screen
No. Parameters Note
1
On/Off
On
indicates that the smart cooling product is started and
Off
indicates that the smart cooling product is shut down.
2
01, 02, 03
Indicates the smart cooling product address. 01 is the master one
and the rest are all slave ones.
NOTE
If the master one offline, the teamwork networking failed.
3
Active/Stand
Active: properly responds to the requirement control.