FusionModule5000 Smart Modular Data Center
Commissioning Guide
6 Commissioning the Management System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
78
Check Method
Normal Connection
Status
Follow-up Procedure
when the aisle door is closed.
Step 5
Check functions of the magnetic lock.
Table 6-20
Function commissioning
Check Method
Normal Connection
Status
Troubleshooting
When the aisle door is
normally closed, check
whether there is a door open
alarm on the ECC800.
There is no door open
alarm on the ECC800.
If a door open alarm is reported
when the door is closed,
relocate the magnetic lock and
magnet to minimize the
deviation until the door open
alarm is cleared.
----End
6.6.4 NetEco Management
6.6.4.1 Connecting the Communications Cable
Procedure
Step 1
Connect the communications cable to the WAN_1 port on the ECC800.
Figure 6-22
Connecting the communications cable
----End
6.6.4.2 Setting NetEco Parameters
When the smart module can be connected to the NetEco, perform the following steps to
configure parameters.