FusionModule5000 Smart Modular Data Center
Commissioning Guide
5 Commissioning the Cooling System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
28
Menu
Parameter
Description
Configuration
Principle
the actual
networking mode.
Otherwise, the
teamwork control
function will be
unavailable.
control over an FE port.
Number of smart
cooling products in
this group
Number of the
smart cooling
products in this
group (1 to 32 can
be set).
Total number of the
smart cooling products in
this group.
Number of running
smart cooling products
in this group
Number of active
units in a group.
The value ranges
from 1 to
Number of smart
cooling products
in this group
.
The host allocates
running units by smart
cooling product unit
address in ascending
order, which is from 1 to
32. The rest will become
the standby ones.
System Settings
(visible for
V200R002
version)
Humidifying function
The humidifying
function can be
set to
Enable
,
Disable
, or
Enabled when
active power
.
Enable
indicates that the
electric humidifier will
be started when the
ambient humidity is
lower than the certain
humidity range of the
humidity set point.
Disable
indicates that the
electric humidifier will
not be started.
Enabled
when active power
indicates that the electric
humidifier will be started
when the main power is
active and the ambient
humidity is lower than
the certain humidity
range of the humidity set
point.
Dehumidifying
function
The
dehumidifying
function can be
set to
Enable
,
Disable
, or
Enabled when
active power
.
Enable
indicates that the
dehumidification
function will be enabled
when the ambient
humidity exceeds the
certain humidity range of
the humidity set point.
Disable
indicates that the
dehumidification
function will not be
enabled.
Enabled when
active power
indicates