6 Commissioning the Management System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
102
Figure 6-42
Setting running parameters
Step 4
Choose
Monitoring > Cooling > Running Parameters
. In the
Cooling Capacity
Management
area, set the parameters related to cooling capacity management for the
watercooled smart cooling product, such as the target cooling load factor and recommended
supplywater temperature statistics cycle.
Figure 6-43
Setting cooling capacity management parameters
----End
6.6.7.2 Querying Cooling Capacity Parameters
Prerequisites
The chilled water smart cooling product is successfully connected to the ECC800.
Procedure
Step 1
Log in to the ECC800 WebUI as the administrator.
Step 2
Choose
Monitoring
>
Cooling
to access the
Running Info
page.
Step 3
Query the cooling information about the smart module, such as
Cooling capacity for smart
module
,
Supply water temperature for smart module
,
Return water temperature for
smart module
, and
Maximum cooling capacity for smart module
, as shown in