FusionModule5000 Smart Modular Data Center
Commissioning Guide
6 Commissioning the Management System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
103
Figure 6-44
Cooling capacity parameters
Step 4
Choose
Monitoring
>
System
. Click
Cooling Capacity Information
on the
Running Info
tab page to query the cooling capacity parameters of the smart module.
Step 5
If the cooling load factor of the smart module exceeds 95%, a cooling margin insufficient
alarm will be raised, which will be cleared when the cooling load factor is smaller than 93%.
----End