FusionModule5000 Smart Modular Data Center
Commissioning Guide
7 FAQ
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
104
7
FAQ
7.1 WebUI Operations
7.1.1 How to Set and Add the Multi-functional Sensor
If a multi-functional sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the straight-through cable has been connected to the POE port on the
multi-functional sensor, and the other end has been connected to the POE port on the ETH
converter.
Procedure
Step 1
Set multi-functional sensor parameters.
On the WebUI, choose
Monitoring
>
Aisle
>
Multi-Func Sensor Group
>
Multi-Func
Sensor1
>
Running Parameters
, ensure that
Smoke enable
and
Temp enable
are set to
Enable
, set
High temperature alarm threshold
and other parameters as required, and then
click
Submit
.
If multiple multi-functional sensors are connected, commission one multi-functional sensor first and
then commission the other multi-functional sensors in the same way.
Step 2
Check the functions of the multi-functional sensor.
Table 7-1
Function check
Check Method
Normal Connection Status
Temperature and humidity
detection: View the running
information about the
multi-functional sensor on the
WebUI.
You can view the current ambient temperature and
humidity.
Smoke detection: Simulate a
smoky environment.
Start counting time immediately when smoke is
entering the hole. After about 30 seconds, the red