FusionModule5000 Smart Modular Data Center
Commissioning Guide
5 Commissioning the Cooling System
Issue 06 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
36
Figure 5-5
Teamwork settings
Step 2
Set teamwork control parameters.
All teamwork control parameters can be set on the master smart cooling product. Only
Teamwork group No.
,
Air conditioner address
,
Enable teamwork CAN resistor
,
Teamwork function
and
Networking mode
can be set on slave smart cooling products.
Other parameters of the slave units will be modified by the master unit synchronously.
describes how to set the parameters.
Table 5-5
Teamwork settings
Parameter
Description
Configuration
Principle
Default
Value
Teamwork
group No.
Set the assigned
teamwork control
number.
The number of the
teamwork controlled
group, which is the same
for all the devices in the
group.
1
Air conditioner
address
Set the assigned smart
cooling product address.
Smart cooling product
addresses should be
different from each other.
NA
Enable
Teamwork
CAN resistor
Indicates the build-out
resistor status of each
smart cooling product in
a teamwork group. Set
the parameter if
CAN
network
is used.
Set this parameter to
No
for non-teamwork
scenarios.
For teamwork
scenarios, set this
parameter to
Yes
for
the first and last smart
cooling products in a
teamwork group, and
set it to
No
for other
smart cooling products.
No
Teamwork
function
Disable or enable the
teamwork function. If the
teamwork function is
Set this parameter based
on the onsite device heat
Disable