6 Maintenance and Troubleshooting
Issue 05 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
98
6.2.3 Alarm Reference for the Independent Deployment AI/DI
Unit
For details about the alarms and troubleshooting for the eight ports on the Independent Deployment
AI/DI Unit, see the alarm description and troubleshooting instructions provided for the AI/DI_1 port on
the AI/DI expansion card.
6.2.3.1 MUE06A_Board Not Exist
Description
This alarm is generated when cables are not securely connected, the power supply is abnormal,
or the board is faulty.
Attribute
Alarm ID
Alarm Severity
Alarm Type
22656
Set to
Major
by default.
Equipment alarm
Impact on the System
After this alarm is generated, the WebUI stops updating parameter values of undetected
equipment and fails to send configuration signals. Maintain the equipment immediately.
Possible Causes
Cables are not securely connected.
The power supply is faulty.
The board is faulty.
Procedure
Step 1
Check that cables are properly connected.
Step 2
Rectify faults in the power supply.
Step 3
Replace the faulty board.
----End
Clearing
This alarm is cleared when the board is properly connected and the communication between
the board and the ECC500 resumes.