4 Installation and Commissioning
Issue 05 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
51
Set the device address for the ABB OTM ATS. The addresses of devices connected to a same
port must be unique. When creating an ABB OTM ATS on the ECC500 WebUI, enter this
value in
Equipment Address
.
Step 7
Press
ESC
to return to the home screen.
----End
4.4.11 Setting the PD510 Coulometer Device Address
Prerequisites
The device address planned for the PD510 coulometer is obtained.
The PD510 coulometer is powered on.
Procedure
Step 1
Hold down
PROG/ESC
for 3s on the display panel of the PD510 coulometer and enter the
correct password.
The preset password is 1000. To protect the access security, change the password after logging in to the
coulometer for the first time.
Step 2
Press
ENTER
.
Step 3
SyS
is displayed. Then press
ENTER
.
Step 4
Set communications parameters.
Table 4-10
Parameter description
Parameter
Description
Addr
Indicates the device address planned for the PD510
coulometer. The devices with the same address cannot
connect to the same port. When creating a PD510 coulometer
on the ECC500 WebUI, enter this value in
Equipment
Address
.
bAUd
Indicates the baud rate. The default baud rate is 9600.
Pro
rtu
DataBit
,
StopBit
, and
Parity
for the PD510 coulometer cannot be set on the WebUI. Their
values are
8
,
1
, and
None
respectively.
Step 5
After the modification, hold down
PROG/ESC
for 3s to return to the home page so that the
configuration is completed.
----End