ECC500
User Manual
5 UI Description
Issue 05 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
58
Figure 5-8
Adding a T/H sensor
The setting example indicates that the T/H sensor is connected to the COM5 port of the
RS485 card in slot 3 of the ECC500. If the T/H sensor is connected to another port, set the
slot number for the connected port.
Table 5-2
T/H sensor parameters
Parameter
Setting
Communication
Board Slot
Select
3
from the drop-down list box.
Communication
Board COM
Select
5
from the drop-down list box.
Equipment Address
In this example, set
Equipment Address
to
1
. Set the actual
device address of the T/H sensor during operations.
Timeout
The default timeout interval is 2s. Set the parameter to the required
value.
Step 6
Click
Add Equipment
.
----End
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.