5 UI Description
Issue 05 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
76
Parameter
Setting
Communication
Board COM
Select
5
from the drop-down list box.
NOTE
The setting example indicates that the PDU8000 is connected to the COM5
port of the RS485 card in slot 3 of the ECC500. If the PDU8000 is
connected to another port, set the number of the connected port.
Equipment Address
In this example, set
Equipment Address
to
1
. Set the actual
device address of the PDU8000 during operations.
Timeout
The default timeout interval is 2s. Set the parameter to the required
value.
Step 4
Click
Add Equipment
.
----End
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.
5.2.8 Adding an ABB OTM ATS
Prerequisites
An ATS is connected to the ECC500. The ATS and ECC500 have been powered on.
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
After an ATS is connected to the ECC500, add the ATS on the ECC500 WebUI.
Procedure
Step 1
Log in to the ECC500 WebUI.
Step 2
Choose
Home
>
Equipment Manage
.
Step 3
Select
ATS
from the
Equipment Type
drop-down list box and set device parameters, as
describes the setting methods.