4 Installation and Commissioning
Issue 05 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
48
4.4.6 Setting the UL33 UPS Device Address
Prerequisites
The UL33 UPS has been powered on.
Procedure
Step 1
The default address of the UL33 UPS is
1
and does not need to be set. Fill the address in
Equipment Address
when creating a UL33 UPS on the ECC500 collector.
----End
4.4.7 Setting the NetCol5000-A Device Address
Prerequisites
You have obtained the device address assigned to the NetCol5000-A.
The NetCol5000-A has been powered on.
Procedure
Step 1
Tap
Settings
on the NetCol5000-A home screen.
Step 2
Enter the administrator user name and password and tap
on the screen.
The preset user name and password for the NetCol5000-A are respectively
Admin
and
000001
. To
ensure access security, change the password upon first use.
Step 3
Tap
Com Settings
.
Step 4
Set
Com address
and
Baud Rate
.
Table 4-7
Parameter description
Parameter
Setting
Com address
Indicates the device address planned for the NetCol5000-A.
The addresses of devices connected to the same collector port
must be unique. When creating a NetCol5000-A on the
ECC500 WebUI, enter the value in
Equipment Address
.
Baud Rate
Retain the default value
9600
.
The
DataBit
,
StopBit
, and
Parity
for the NetCol5000-A cannot be set on the WebUI. Their
default values are
8
,
1
, and
None
respectively.
----End