ECC500
User Manual
4 Installation and Commissioning
Issue 05 (2020-03-16)
Copyright © Huawei Technologies Co., Ltd.
50
The preset user name and password for the PDU8000 are respectively
admin
and
000001
. To ensure
access security, change the password upon first use.
Step 3
Tap
Communication
.
Set
Serial port baud rate
and
Serial port address
.
Table 4-9
Parameter description
Parameter
Setting
Serial port baud rate
Retain the default value
9600
.
Serial port address
Indicates the device address assigned to the
PDU8000. The addresses of devices
connected to a same port must be unique.
When creating a PDU8000 on the ECC500
WebUI, enter this value in
Equipment
Address
.
The
DataBit
,
StopBit
, and
Parity
for the PDU8000 cannot be set on the WebUI. Their default
values are
8
,
1
, and
None
respectively.
----End
4.4.10 Setting the ABB OTM ATS Device Address
Prerequisites
You have obtained the device address assigned to the ABB OTM ATS.
The ABB OTM ATS has been powered on.
Procedure
Step 1
On the display panel of the ABB OTM ATS, press
.
Step 2
Press
to move the cursor to
Device Configuration
.
Step 3
Press
.
Step 4
Enter the password and press
.
The preset password is 0001. To ensure access security, change the password upon first use.
Step 5
Press
to move the cursor to
Modbus
.
Step 6
Press
. On the Modbus parameter setting screen, set communications parameters.