63
LP- 428 REV. 9.2.14
Fault Code TT
Temperature Blocking TT Demand
TEMPER BLOCKING
PUMP ON TT
This screen indicates a temporary hold on the burner. There is a demand on the boiler, the pump is powered on, but the
temperature of the water at the supply sensor is too high for the boiler to ignite. This occurs because the water tempera-
ture measured by the supply sensor is higher than the boiler temperature
– ignition diff setting. This error will clear itself
when the water temperature measured by the supply sensor is less than the boiler temperature
– ignition diff setting.
Fault Code DHW
Temperature Blocking DHW Demand
TEMPER BLOCKING
PUMP ON DHW
This display indicates a temporary hold on the burner. There is a demand on the boiler from the DHW circuit for heat,
the pump is powered on, but the boiler supply sensor indicates that the water temperature is too high to ignite. This is a
temporary hold on the burner only and all other functions will remain functioning properly. This error will clear itself when
either the boiler supply temperature drops below the BOILER SUPPLY minus boiler supply differential (5
o
F) or DHW
SETPOINT is satisfied and no longer calls for heat.
Fault Code LEO
LOW WATER LEVEL
PUMP OFF LEO
Water level in the boiler is low.
1. Check boiler feed water system to be sure it is supplying make-
up water to the boiler system.
2. Be sure all air is bled from the system.
3. Check for leaks in the boiler and system piping and repair as
necessary.
4. Inspect low level switch and wiring for damage and repair as
necessary.
Fault Code FLU
HIGH FLUE PRESS FLU
PUMP ON
This display indicates that there is excessive flue
pressure. This code resets automatically after
the high pressure condition is resolved. The sec-
ond line indicates the status of the pump.
1. Assure that the flue is not blocked.
2. Check the switch wiring by applying a jumper in place of the
switch. If the code clears with the jumper in place, REPLACE the
flue switch and connect the wires to the new switch BEFORE
running boiler.
WARNING:
Do not use jumper to remedy an FLU error. Faulty switch MUST be replaced. Failure to do so could result in serious injury or death.
Fault Code LOU
24 VOLT LOW LOU
PUMP ON
This display indicates that
the 24 volt power supply on
the control is damaged or
overloaded. This code
resets automatically if it is
the result of an overload and
that overload condition is
removed. The second line
indicates the status of the
pump. Note that while 24
volt power is low, the pump
output will be on.
1. Check line voltage. It must be between 100 and 128 volts.
2. If available, connect PC, and using HTP service software check the 24v supply
display in the lower left corner of the screen. The number displayed here must be
greater than 128 and should be no greater than 250. Use this as a troubleshooting guide
as you follow the steps below.
3. Remove the 10 pin Molex connector from customer connection board. If the message
clears, then the problem is with the external sensor wiring. Examine the external sensor
wiring for shorts to the ground, repairing as necessary. If the message is still present
and the boiler is so equipped, disconnect the UL 353 low water cut-off to see if the
message clears. Replace the faulty part. Check the low voltage wire harness in boiler for
shorts to ground.
4. If a message only occurs when the burner tries to light, check the gas valve for exces-
sive current draw.
5. If a message is present with the low voltage harness disconnected from the 926
control board, replace the 926 control board.
Fault Code F00
WATER HIGH TEMP F00
PUMP ON
This display indicates if the water in the boiler
has overheated. This code indicates a serious
safety issue and the boiler will not restart until it
cools sufficiently and a technician repairs the
cause of overheating and pushes the RESET
button on the display. This is a serious situation
and is indicated by the red light on the display
illuminating and the word LOCKOUT flashing on
the display. During this lockout fault, the pump
will be on as indicated on the second line in an
effort to cool the boiler down.
1. Check circulator pump operation
2. If the circulator pump is running, be sure that there is water in
the system and that the water is moving through the system as
intended. Be sure that all correct ball valves and or zone valves are
open or closed as intended.
3. Observe the temperature/pressure gauge. If the water is not too
hot and this message is displayed, check the wiring to the water
ECO sensor and repair if necessary. If the wiring is ok and this code
is still present and the water is not excessively hot, replace the ECO
sensor.
Содержание MODCON1000
Страница 40: ...40 LP 428 REV 9 2 14 E GAS VALVE Figure 22 Mod Con 1000 Gas Valve ...
Страница 46: ...46 LP 428 REV 9 2 14 Figure 25 Figure 26 Cascade Resistor Plug Installation Detail ...
Страница 47: ...47 LP 428 REV 9 2 14 Figure 27 Mod Con Cascade Master and Follower Wiring ...
Страница 48: ...48 LP 428 REV 9 2 14 Figure 28 Mod Con Internal Connection Diagram LP 428 K ...
Страница 70: ...70 LP 428 REV 9 2 14 Figure 31 MOD CON 1000 External Parts Blowout ...
Страница 71: ...71 LP 428 REV 9 2 14 Figure 32 MOD CON 1700 External Parts Blowout ...
Страница 72: ...72 LP 428 REV 9 2 14 Figure 33 ...
Страница 73: ...73 LP 428 REV 9 2 14 Figure 34 LP 445 S ...
Страница 74: ...74 LP 428 REV 9 2 14 Figure 35 LP 428 V ...
Страница 75: ...75 LP 428 REV 9 2 14 Figure 36 ...
Страница 78: ...78 LP 428 REV 9 2 14 ...
Страница 79: ...79 LP 428 REV 9 2 14 ...
Страница 80: ...80 LP 428 REV 9 2 14 MAINTENANCE NOTES ...