Required tools for installation
The customer needs to provide the screws, cage nuts, and related tools for mounting the rails into the rack.
While installing additional components in the system, HPE recommends to install the following tools:
• T-30 Torx screwdriver (processor or heatsink installation or removal)
• 1/4" flathead screwdriver (used to release the processor from a heatsink)
• T-10 Torx screwdriver (all other components that utilizes screws)
Mounting the system on a rack
WARNING:
Important safety information
Electrostatic Discharge (ESD) can damage the electronic components. Ensure that you are properly
grounded (earthed) before beginning any installation procedure.
Qualified individuals who know the procedures, precautions, and equipment hazards that contains hazardous
electrical circuits must perform this installation.
Procedure
1.
The rail kits, when installed, form only a shelf for the StoreEasy 1X60 to rest on. The StoreEasy 1X60 is
not attached to the rail by any other means. Use extreme caution when pulling the StoreEasy 1X60 out
from the rack. The storage system can slip and fall, which may cause damage or injury to the StoreEasy
1X60 Storage. HPE is not responsible for any damage or injury caused by mishandling of StoreEasy 1X60.
2.
Ensure that the rack is leveled and stable before working on the rack. The leveling jacks (feet) must extend
to the floor and the full weight of the rack must rest firmly on the floor.
3.
Ensure that the rack has anti-tip measures such as, floor-bolting, anti-tip feet, ballast, or a combination of
the measures, specified by the rack manufacturer and applicable codes.
4.
Ensure that sufficient personnel are available to support one or more products during the installation
process. HPE recommends you use an appropriate lifting device as an installation aid.
5.
Ensure that the rack is loaded from bottom to top, with the heaviest appliances at the bottom to make the
rack steady.
6.
Avoid overloading the branch circuit that provides power to the rack. The total rack load must not exceed
80 percent of the branch circuit rating.
16
Required tools for installation