Regulatory information 81
Regulatory information
HP POD 20c regulatory compliance
The HP POD 20c complies with the following regulatory standards.
Standard Certification level
Standard title
IEC/EN
60950
"Intertek Tested and
Certified"
•
IEC/EN 60950—
Standard for Safety Information Technology
Equipment, Part 1: General Requirements
, Issue: 2006
•
IEC/EN 60950—
Standard for Safety Information Technology
Equipment, Part 22: Equipment to be Installed Outdoors
, Issue:
2006
IBC 2009
Designed to Comply
With the applicable
requirements
2009 International Building Code
, © 2010 International Code
Council, Inc.
Safety and IEC compliance
The HP POD 20c is examined, tested, and found to be in compliance with IEC/EN 60950 Part 1 and Part
22 as an Information Technology Product. For more information, see "HP POD 20c regulatory compliance
)."
The HP POD 20c is not suitable for long-term human occupancy. The HP POD 20c is Listed as a Product that
provides service access areas for periodic maintenance and service. These areas must be used only by
owner-authorized and qualified personnel who are trained in the maintenance and service of the HP POD
20c components.
IMPORTANT:
Before installing the HP POD 20c, consult your local Authorities for applicable
regulations and to review site-specific location guidelines. If needed, obtain any necessary
permits.
Additional considerations for safety and Electrical compliance are as follows:
•
The HP POD 20c is Certified as an Information Technology Product to IEC/EN 60950 Part 1 and Part
22.
•
The HP POD 20c is evaluated as a "non-inhabitable product" that provides "service access" areas for
customer-authorized, qualified, and trained service personnel.
•
The electrical connections of the HP POD 20c are evaluated as feeder connections for connection to an
existing facility, and are not suitable as "service entrance" for connection to the utility.
•
The HP POD 20c is designed for stationary installation outdoors in a Pollution Degree 3 environment,
in restricted access locations, with field wiring terminals provided for permanent supply connections.
•
The HP POD 20c meets the following ratings.
Feature
Specification
Category
Rated Overvoltage Category III
Protection
Surge protection device