Removal and replacement procedures  67 

Switches 

ECS power switch 

The ECS power switch is located on the ECS cabinet door. 
You need a screwdriver to remove and replace the ECS power switch. 

 

Removing the ECS power switch 

1.

 

Remove the ECS power switch (1). 

2.

 

Remove the four screws from the door interlock plate (2). 

3.

 

Remove the switch body from the interlock plate (3). 

4.

 

Disconnect the wires. 

 

 

Replacing the ECS power switch 

1.

 

Reconnect the wires. 

2.

 

Insert the switch body into the interlock plate (1). 

3.

 

Insert the four screws into the door interlock plate (2). 

Содержание Performance Optimized Datacenter 20c

Страница 1: ...Datacenter 20c Maintenance and Service Guide International Abstract This guide provides maintenance and service instructions for the HP Performance Optimized Datacenter 20c HP POD 20c Part Number 732011 001 June 2013 Edition 1 ...

Страница 2: ...ithout notice The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services Nothing herein should be construed as constituting an additional warranty HP shall not be liable for technical or editorial errors or omissions contained herein ...

Страница 3: ...Control relay module 22 Door position devices 23 Limit switch 23 Electrical 24 Busway drop box 24 Fans 28 IT cooling fan 28 Cooling fan bank assembly 30 Cooling fan controller 32 Ventilation fan 34 Filters 35 Heat exchanger air filters 35 VESDA filter 36 Rittal SK 3243 ventilation fan filter 38 Fire alarm activation 39 Manual call point safety glass replacement 39 Indicators 42 ECS touchscreen and...

Страница 4: ...74 Life safety 75 Access control 76 Third party components 76 Specifications 77 General HP POD 20c specifications 77 Electrical specifications 77 Water specifications 78 Rack specifications 78 Thermal and air flow performance 78 Environmental specifications 78 Optional features specifications 79 Contacting HP 80 Before you contact HP 80 HP contact information 80 Regulatory information 81 HP POD 20...

Страница 5: ...onent Description 1 Heat exchanger access hatches Enables access to the overhead heat exchangers 2 Emergency egress door Provides access to the POD in the event of an emergency 3 Personnel access door Provides access to the POD 4 Facility chilled water return Facilitates the return of chilled water to the POD 5 Facility chilled water supply Facilitates the supply of chilled water to the POD Life s...

Страница 6: ...g the interior and exterior fire strobe lights and the optional fire suppression system 7 Fire suppression abort button Aborts the fire suppression system A fire suppression abort button is located next to each personnel door 8 Fire alarm manual button Enables manual initiation of the fire system which includes activating the interior and exterior fire strobe lights and the optional fire suppressi...

Страница 7: ...onents Side view shown Item Component Description 1 Fire strobe light Indicates a fire alarm condition within the HP POD 20c 2 Fire horn Indicates a fire alarm condition within the HP POD 20c 3 Optional EPO button Manually triggers an EPO shutdown within the HP POD 20c ...

Страница 8: ...cabinet2 Converts main power from 480V to 415V for POD operation 4 380 415 VAC WYE 3 phase 320 A Feed A and B power for IT critical loads busways and house power 1 The demarcation box and the fire box are communication data points that are provided on the POD by HP Connecting these data points is the responsibility of the customer unless an approved Statement of Work is initiated 2 This cabinet is...

Страница 9: ...Illustrated parts catalog 9 Side view shown Critical IT and transformer cabinet Front view shown External panel labels ...

Страница 10: ...Provides the order for disconnecting the electrical panels 4 Short circuit current label States that the design of the POD can withstand the available fault current and describes the electrical system 5 Arc flash warning Provides a reminder to users of the danger of arc flash and required PPE 6 Grounding label Indicates the location of the grounding electrode connection point Side view shown Item ...

Страница 11: ...the electrical system 6 Arc flash warning Provides a reminder to users of the danger of arc flash and required PPE Internal panel labels Front view shown Item Electrical safety label Description 1 Power feeders caution label Cautions users about phase rotation for all power feeders 2 Wire color code Lists the 380 415 Y 200 240 V color codes Brown Phase A L1 Black Phase B L2 Grey Phase 3 L3 Blue Ne...

Страница 12: ...rown Phase A L1 Black Phase B L2 Grey Phase 3 L3 Blue Neutral Green and yellow Equipment ground 3 Panel schedule circuit breaker table fuse list Lists the layout and designation for all circuit breakers and lists all fuse types and sizes Control cabinet component identification Item Component Description 1 VESDA air sampling smoke detection unit An early warning laser scan smoke detection unit ...

Страница 13: ...her house panel components 5 Dual power supplies with battery backup Provides 24 V DC power to the PLC LED lighting and ECS systems HP POD 20c racks The standard HP installed rack is a 50U rack The HP POD 20c contains a total of 10 IT racks During maintenance if you remove filler panels for maintenance purposes you must replace them Cold aisle to hot aisle separation must be maintained CAUTION If ...

Страница 14: ... distance The maximum rack face to cold aisle wall distance is 39 5 inches In the figure X represents any protrusion into the cold aisle starting from the rack face of the installed IT component for example the bezel Y represents cold aisle clearance The cold aisle clearance dictates the maximum depth D of any installed IT component To find the maximum cold aisle clearance calculate 100 33 cm 39 5...

Страница 15: ...EENS FRAME w FILTER 595108 001 SPS MAINT KIT FILTERS AT979A 612980 001 SPS BUS BAR 5 POLE 3M 612981 001 SPS END CAP 612982 001 SPS HOUSING COUPLER 612983 001 SPS MOUNTING STUD M10 616611 001 SPS POD FAN 616612 001 SPS FAN TRAY ASSY 616613 001 SPS CA FAN TRAY ASSY 616614 001 SPS POD FAN PWR SUP CHASSIS 616615 001 SPS POD PWR SUPPLY 637088 001 SPS CPU TOUCH SCREEN 637090 001 SPS TERMINAL DIGITAL OUT...

Страница 16: ... the following table are electrical components that must be replaced by a qualified electrician IMPORTANT A licensed electrician must connect the power according to all local and national electrical codes and must comply with manufacturer specifications Spare part number Description 660784 001 SPS Breaker 660785 001 SPS Breaker 660786 001 SPS Breaker Shield 660787 001 SPS Breaker 660788 001 SPS Fu...

Страница 17: ...ed electrician Failure to comply with these instructions can impact your warranty and or result in equipment damage Safety and IEC compliance The HP POD 20c is examined tested and found to be in compliance with IEC EN 60950 Part 1 and Part 22 as an Information Technology Product For more information see HP POD 20c regulatory compliance on page 81 The HP POD 20c is not suitable for long term human ...

Страница 18: ...system specifically designed for this HP product in compliance with national standards The HP standard suppression system includes a Novec 1230 clean agent system However if the customer or local Authorities require specific modifications or a replacement HP can assist in these actions at the expense of the customer HP does not certify that the fire suppression system that is installed in the HP P...

Страница 19: ... 19 Removal and replacement procedures Buttons EPO button One EPO button is located on the POD interior near the main exit and an optional second EPO button is located on the POD exterior Removing the EPO button 1 Open the tamper cover ...

Страница 20: ...point housing 1 and then remove the call point housing cover 2 3 Remove the retention device from the back of the EPO button 1 and then remove the EPO button 2 Replacing the EPO button 1 Replace the EPO button 1 and then replace the retention device on the back of the EPO button 2 ...

Страница 21: ...the components The methods for attaching components to DIN rails include the following Mechanical sliding of the component onto the DIN rail which requires the removal of the DIN rail Mechanical snapping of the component onto to the DIN rail with or without elastic deformation Mechanical release of the component from the DIN rail WARNING A licensed electrician must determine the electrical isolati...

Страница 22: ...ment Control relay module The HP POD 20c uses analog and digital control relays to communicate sensor parameters to the ECS for overall POD control and reporting features You need a screwdriver to remove and replace the control relay module Removing the control relay module 1 Label the wired connections or take a picture to remember which wires to reconnect to the control relay module 2 Using a sc...

Страница 23: ...it switch Limit switches are part of the door position indication within the ECS All doors have limit switches You need a screwdriver to remove and replace the limit switch Removing the limit switch 1 Remove the four screws from the limit switch assembly 1 2 Disconnect the wires 3 Remove the limit switch assembly 2 ...

Страница 24: ...cal Busway drop box The internal electrical busways provide a location to connect each of the drop boxes which then power the PDUs Stagger the drop boxes on the electrical busways by connecting one drop box to busway 1 and connecting the next drop box to busway 2 A staggered configuration enables load balancing with the rack equipment and is necessary to ensure redundancy ...

Страница 25: ...place the busway drop box Removing the busway drop box 1 Turn the power off by opening both breakers on the busway drop box 1 2 Disconnect the PDUs that are connected to the busway drop box 2 3 Use a socket wrench to loosen and remove the bolt securing the busway drop box to the retaining hardware bracket 1 4 Slide the hardware bracket to the right along the busway completely disconnecting it from...

Страница 26: ...l busway where you want to replace the busway drop box 1 2 Note the required rotation indicated on the drop box insert the drop box into the drop box bracket on the electrical busway and then rotate the drop box 90 until it locks into place 2 CAUTION To prevent damage to the drop box and ensure that the drop box engages properly be sure that the drop box is completely flush to the busway If a drop...

Страница 27: ... 27 4 Secure the busway drop box to the retaining hardware bracket by using a socket wrench to insert and tighten a bolt 4 5 Connect the PDUs to the busway drop box 1 6 Turn the power on by closing both breakers on the busway drop box 2 ...

Страница 28: ... before replacing the fan De energizing working fans reduces the IT cooling airflow within the zone Take this into consideration when deciding whether to continue operating IT equipment within the affected zone HP recommends powering down all of the IT in the zone IMPORTANT HP recommends leaving the fans in AUTO mode during normal operation The HP POD 20c has 3 banks of 6 fans for a total of 18 fa...

Страница 29: ...three screws that secure the fan in the assembly 1 and then partially remove the fan by pulling it straight out 2 5 Disconnect the wire 6 Remove the fan from the assembly Replacing the variable speed IT cooling fan 1 Connect the wire 2 Insert the fan into the assembly and push until the fan is fully seated 1 ...

Страница 30: ...an bank to the AUTO mode of operation Cooling fan bank assembly There are three fan banks in each cooling zone CAUTION Power must be removed from the fan power assembly before removing or replacing a fan or fan bank You need a screwdriver to remove and replace the cooling fan bank assembly Removing the cooling fan bank assembly HP recommends leaving the fans in AUTO mode during normal operation ...

Страница 31: ...ero 3 Unseat both power supplies from the fan power assembly 4 Remove the cooling fan bank wire harness 1 5 Remove the six screws that secure the cooling fan bank 2 6 Remove the cooling fan bank by pulling it straight out 3 Replacing the cooling fan bank assembly 1 Insert the cooling fan bank 1 2 Secure the cooling fan bank with six screws 2 ...

Страница 32: ... controller is located in the ceiling in front of the fan banks CAUTION Removing the cooling fan controller makes all fans within the affected zone inoperable Take this into consideration when deciding whether to continue operating IT within the affected zone HP recommends powering down all IT in the zone You need a screwdriver to remove and replace the cooling fan controller Removing the cooling ...

Страница 33: ...er into the ceiling 1 2 Replace the four screws 2 3 Reconnect the outbound 24 V dc fan power cables 4 Reconnect the inbound 230 V power connectors 5 Return power to the controller 6 Take manual control of the fan speed in the affected zone from the ECS panel 7 Verify that the fans work properly 8 Return the fan bank to the AUTO mode of operation ...

Страница 34: ...tion to the electrical components within the ECS and electrical cabinets Rittal SK 3243 You do not need any tools to remove and replace the ventilation fan Removing the Rittal SK 3243 ventilation fan 1 Open the ECS cabinet door 2 Disconnect the fan wires 3 Rotate the fan module counterclockwise to unseat it from the screwless spring terminal 1 4 Pull the fan module forward to remove it 2 ...

Страница 35: ...ect the fan wires 4 Insert the ventilation fan into the ventilation fan cut out hole 5 Close the ECS cabinet door Filters Heat exchanger air filters There are two heat exchanger air filters per cooling zone for a total of six filters You do not need any tools to remove or replace the heat exchanger air filter Removing the heat exchanger air filter 1 Pull the locking tabs away from the filter to re...

Страница 36: ...he filter up to the top of the frame 2 Push in the bottom corners of the filter until the locking tabs engage and the filter clicks into place VESDA filter The VESDA filter sensor notifies you through the ECS when a filter must be changed HP recommends periodically inspecting and changing each VESDA filter A VESDA filter can be replaced during normal HP POD 20c operation You need a Phillips head s...

Страница 37: ...ter 1 Remove the filter cover on the front of the VESDA unit 2 Remove the 10mm screw that secures the VESDA filter 1 and then remove the filter 2 Replacing the VESDA filter 1 Insert the new VESDA filter 1 and then replace the 10mm screw that secures the filter 2 ...

Страница 38: ...lter is located behind the louvered grille IMPORTANT Check the fan filter quarterly to be sure that it is clean You do not need any tools to remove and replace the ventilation fan filter Removing the Rittal SK 3243 ventilation fan filter 1 Lift the latch on the louvered grille and pull forward to open it 1 2 Remove the old filter 2 ...

Страница 39: ...the new filter 1 2 Close the louvered grille 2 Fire alarm activation Manual call point safety glass replacement The manual call point enables you to signal to other occupants of the POD that a fire or other emergency exits You need the manual call point key to remove and replace the manual call point ...

Страница 40: ...ures 40 Removing the manual call point glass or flexi element 1 Insert the manual call point key into the holes that are located on the bottom of the call point box 2 Remove the manual call point key 1 and then disengage the bezel 2 ...

Страница 41: ...e grasping the sides of the bezel 1 slide it down to expose the glass or flexi element 2 4 Remove the manual call point glass or flexi element Replacing the manual call point glass or flexi element 1 Insert the replacement glass or flexi element ...

Страница 42: ... and EPO indicators are located on the door to the control panel The touchscreen enables you to easily configure the environmental parameters access data and monitor environmental life safety and access control conditions within the HP POD 20c The EPO indicators provide EPO status The EPO key control and EPO reset button enable you to adjust the EPO system mode ...

Страница 43: ...hat the EPO system is armed and operational 7 EPO reset button Blue Resets the EPO system when pressed 8 EPO mode key control Enables you to select the EPO mode 9 EPO shutdown button Red Initiates a manual EPO event 10 Light test button Tests all the EPO LED indicators when pressed 11 EPO bypass mode indicator Green Indicates that the EPO shut down functionality is bypassed 12 EPO test mode indica...

Страница 44: ...ght into the mounting base 1 2 Attach the contact block to the mounting base 2 3 Attach the screw to the mounting base 3 Fluid system components The removal of any HP POD 20c installed chilled water fluid system components that compose or penetrate the physical integrity of the fluid system requires the following Complete shutdown of the HP POD 20c Isolation of the HP POD 20c from the site chilled...

Страница 45: ...ng installed sensors o Chilled water supply and return header pressure sensors o Chilled water supply and return header temperature sensor o Chilled water flow meter sensor Chilled water supply and return header pressure sensors The HP POD 20c contains two chilled water pressure sensors One is located in the chilled water supply header and one is located in the return header The chilled water supp...

Страница 46: ...the sensor as it was before removal 2 Connect the sensor to the sensing tube 3 Using a wrench rotate the sensor retaining nut clockwise to tighten it 4 Reconnect the sensor wiring Chilled water flow sensor Removing the chilled water flow sensor 1 Label the wired connections or take a picture to remember which wires to reconnect to the chilled water flow sensor ...

Страница 47: ...nsor 1 Reference your notes on where to reconnect the wires to the chilled water flow sensor 2 Reconnect the sensor wiring 3 Insert the sensor into the water piping 1 4 Using a wrench rotate the sensor locking gland clockwise to tighten it 2 Chilled water system temperature sensor The HP POD 20c contains two chilled water header temperature sensors One is located in the chilled water supply header...

Страница 48: ...re sensor from the chilled water system 1 Identify the location of the sensor to be replaced and remove enough header insulation to uncover the sensor 2 Remove the sensor cover 3 Label and disconnect the sensor wiring 4 Rotate the immersion sleeve counterclockwise 1 and pull forward to remove the entire sensor from the chilled water header 2 Replacing the temperature sensor in the chilled water sy...

Страница 49: ...d in the chilled water supply header and one is located in the chilled water return header You need a screwdriver to remove and replace the chilled water temperature sensor internal components Removing the chilled water temperature sensor internal components 1 Remove the four screws from the sensor cover 1 2 Remove the sensor cover 2 3 Label and disconnect the sensor wires 4 Remove the two screws ...

Страница 50: ...ture sensor circuit board 2 Replacing the chilled water temperature sensor internal components 1 Replace the chilled water temperature sensor circuit board 1 2 Replace the two screws to secure the chilled water temperature sensor circuit board 2 3 Reconnect the sensor wires ...

Страница 51: ...sor cover 1 Valves External chilled water isolation valve The external chilled water isolation valve is a butterfly valve located on the top of the HP POD 20c You need a wrench to remove and replace the external chilled water isolation valve Removing the external chilled water isolation valve 1 Remove the eight bolts surrounding the valve 1 2 Remove the valve 2 ...

Страница 52: ... eight bolts 2 External pressure gauge isolation valve The external pressure gauge isolation valve is located on top of the HP POD 20c You need an adjustable wrench or an appropriately sized box wrench for installation Removing the external pressure gauge isolation valve 1 Loosen the connection securing the valve 1 2 Remove the valve 2 ...

Страница 53: ...sert the new valve 1 2 Tighten the connection 2 Heat exchanger HP service personnel is required to replace this spare component Please contact HP Services for assistance Humidifier The humidifier is located in the cold aisle humidifier bump out You need a Phillips head screwdriver for installation ...

Страница 54: ...supply line to the humidifier on the HP POD 20c exterior to relieve the water pressure 5 Open and danger tag the associated circuit breaker in the ECS cabinet The circuit breakers are identified on the panel schedule 6 Remove the four screws on the corners of the humidifier cover 1 and then remove the cover 2 7 Locate the power board and disconnect the two internal electrical wires 8 Disconnect th...

Страница 55: ...that secure the humidifier body to the wall 1 and then remove the humidifier 2 Replacing the humidifier 1 Replace the humidifier 1 and then secure the humidifier to the wall with four screws 2 2 Connect the drain 1 3 Connect the humidifier to the water supply line 2 ...

Страница 56: ... wires 6 Replace the humidifier cover 1 and then secure the cover with four screws 2 7 Open the water supply isolation valve on the HP POD 20c exterior 8 Connect the water supply line to the humidifier on the HP POD 20c exterior 9 Close the associated circuit breaker in the ECS cabinet 10 Press the power button on the outside of the humidifier to power up the humidifier ...

Страница 57: ...need a screwdriver to remove and replace the LED light Removing the LED light You need a screwdriver to remove and replace the LED light 1 Disconnect power from the LED light 2 Remove the screws 1 3 Remove the LED light assembly 2 Replacing the LED light 1 Place the LED light where you want to secure it 1 2 Insert the screws 2 ...

Страница 58: ...nd return header drain pans one in each of the corresponding cooling zones Removing the chilled water supply and return header drain pan sensor 1 Follow the sensor wire to the associated satellite box Disconnect the wire from the satellite box terminal and note the wire location 2 Pull the wire through from the satellite box to the sensor location and then remove the sensor Replacing the chilled w...

Страница 59: ...ted zone For more information see Removing the fan bank assembly Removing the cooling fan bank assembly on page 30 2 Follow the sensor wire to the associated satellite box Disconnect the wire from the satellite box terminal and note the wire location 3 Pull the wire through from the relay to the sensor location and then remove the sensor Replacing the heat exchanger condensate drain pan sensor 1 P...

Страница 60: ...s The differential pressure sensors are located in the cold aisle You need a screwdriver to remove and replace the differential pressure sensor Removing the differential pressure sensor 1 Label the pressure sensor tube connection locations and then remove the tubes from the differential pressure sensor 2 Label the sensor wire connection locations loosen the screws securing the sensor wires and the...

Страница 61: ...ng the removal procedure 3 Replace the sensor wires according to the connection locations you labeled during the removal procedure and then tighten the screws to secure the sensor wires EPO temperature sensors Two EPO thermisters are located in the hot aisle one in cooling zone 1 and one in cooling zone 3 You need scissors to remove and replace the EPO temperature sensors Removing the EPO temperat...

Страница 62: ... sensor The HP POD 20c contains one humidity sensor It is located in the cold aisle in cooling zone 2 You need a screwdriver to remove and replace the humidity sensor Removing the humidity sensor 1 Remove the four screws that secure the sensor cover 1 and then remove the cover 2 2 Remove the two self tapping screws 3 3 Identify the sensor wires 4 Disconnect the sensor wires ...

Страница 63: ...ity sensor housing from the wall 4 Replacing the humidity sensor 1 Re attach the humidity sensor housing to the wall 1 2 Replace the two self tapping screws 2 3 Reconnect the wires to the hot aisle humidity sensor 4 Replace the sensor cover 3 5 Replace the four screws that secure the sensor cover 4 ...

Страница 64: ...ewdriver for installation Removing the cold aisle temperature sensor 1 Remove the four screws 1 that secure the cold aisle temperature sensor cover and then remove the cover 2 2 Label the cold aisle temperature sensor wires or take a picture to remember which wires to reconnect later 3 Disconnect the wires 4 Remove the two retaining screws and then remove the cold aisle temperature sensor housing ...

Страница 65: ... aisle temperature sensor housing to the wall using the two retaining screws 4 Replace the cold aisle temperature sensor cover 1 5 Replace the four screws that secure the cold aisle temperature sensor cover 2 Temperature sensors hot aisle The HP POD 20c contains three temperature sensors in the hot aisle You need a screwdriver to remove and replace the hot aisle temperature sensors ...

Страница 66: ...ect later 3 Disconnect the wires 4 Remove the two retaining screws and then remove the hot aisle temperature sensor housing from the wall Replacing the hot aisle temperature sensor 1 Reconnect the wires to the hot aisle temperature sensor 2 Reconnect the wires 3 Re attach the hot aisle temperature sensor housing to the wall using the two retaining screws 4 Replace the hot aisle temperature sensor ...

Страница 67: ...CS power switch Removing the ECS power switch 1 Remove the ECS power switch 1 2 Remove the four screws from the door interlock plate 2 3 Remove the switch body from the interlock plate 3 4 Disconnect the wires Replacing the ECS power switch 1 Reconnect the wires 2 Insert the switch body into the interlock plate 1 3 Insert the four screws into the door interlock plate 2 ...

Страница 68: ...Removal and replacement procedures 68 4 Insert the ECS power switch into the interlock plate 3 ...

Страница 69: ...sonnel Cooling system Component to be inspected Task Frequency Capable Party Air filters Inspect and replace as necessary As needed at least quarterly Qualified personnel Air filter differential pressure sensor Inspect and replace as necessary Annually Qualified personnel Cooling system leak check Verify that there is no visible chilled water leakage from the Heat Exchanger CWS piping CWR piping I...

Страница 70: ...erly if not staffed Qualified personnel Conduct an operational check of the external site drain using approximately 5 gallons of water if permissible or possible Annual Qualified personnel Leak detection The HP POD 20c includes six heat exchanger condensate sensors Three sensors are located in the drain pans below each set of heat exchangers and three sensors are located in the chilled water suppl...

Страница 71: ... the ECS Status Overview screen You might need to inspect each zone condensate drain pan to determine the exact location of the leak 2 Power down the IT equipment in the zone where the leak is located 3 Determine the affected heat exchanger 4 Close and danger tag the supply and return valves to the affected heat exchanger If the heat affected exchanger cannot be identified close all the heat excha...

Страница 72: ...nents Quarterly Qualified personnel Check and clear alarm log Quarterly Qualified personnel Inspect and test ECS battery backup system Every 2 years Qualified personnel Electrical Maintenance of the electrical components might require the following Expose personnel to high voltage Allow personnel to come into direct contact with high voltage Power down the POD during the execution of the maintenan...

Страница 73: ...y 2 years Licensed electrician POD SHUT DOWN REQUIRED Service entrance ground connection lug located on the switchboard or landing location torque test Clean and re tighten as necessary Every 2 years Licensed electrician Grounding system bonding jumpers that connect racks to the POD structure and rack to rack torque test Clean and re tighten as necessary Every 2 years Licensed electrician Circuit ...

Страница 74: ... battery backup system Bi annually Authorized technician VESDA Inspect and test VESDA power supply Quarterly Authorized technician Inspect the VESDA pipe network Bi annually Authorized technician Inspect the VESDA filter Replace as necessary Annually Authorized technician Conduct a VESDA pipe integrity smoke test Annually Authorized technician Check the VESDA pipe flow Annually Authorized technici...

Страница 75: ...in the hot aisle Verify all shunt trips on all panels trip Annually Qualified personnel EPO System Test EPO NON FUNCTIONAL TEST Mode Key Switch Test rotate keyed switch through all modes ARMED MODE Verify Power Indicator White Armed Light White BYPASS MODE Verify Bypass Light Green TEST MODE Verify Test Light Amber Press EPO button each in succession and thermal trip to verify Reset Light White Au...

Страница 76: ...urer of the equipment HP will with a defined and signed SOW conduct all maintenance as identified by the original manufacturer Examples of external third party components that HP will conduct all manufacturer specified maintenance with a signed SOW includes External UPS equipment Internal UPS and rack equipment that is purchased from HP is covered by a standard HP warranty and services contract pu...

Страница 77: ...ity of PDUs per HP POD 20c 10 one per rack Maximum quantity of PDUs per HP POD 20c 20 two per rack Maximum power per PDU 30A 17 kW 60A 34 kW Network supported Bulk cable pass through fiber Bulk cable pass through copper External rated DEMARC box 1 The empty weight includes the HP POD 20c structure empty racks PDUs and drop boxes It does not include IT equipment 2 The maximum power depends on the e...

Страница 78: ...c racks AT978A Feature Specification U height 50U Width 54 6 cm 21 5 in Depth 99 cm 39 in Maximum load weight 1 360 7 kg 3 000 lb This specification indicates the maximum clearance for the cold aisle Equipment cannot exceed this measurement Thermal and air flow performance Maximum thermal and air flow performance parameters HP POD 20c specification Air temperature Inlet to rack mounted components ...

Страница 79: ...ft to 30 000 ft For non operating specifications consider the temperature of computer and IT equipment inside the HP POD 20c Optional features specifications Feature Specification Fire suppression 3M Novec 1230 or FM200 fire extinguishing system provided in two canisters main and reserve Card reader 12 key pad with 125 KHz proximity and 13 56 MHz contactless smart card Humidifier Provides 0 9 3 63...

Страница 80: ... registration number if applicable Product serial number Product model name and number Product identification number Applicable error messages Add on boards or hardware Third party hardware or software Operating system type and revision level HP contact information For United States and worldwide contact information see the Contact HP website http www hp com go assistance In the United States To c...

Страница 81: ... areas must be used only by owner authorized and qualified personnel who are trained in the maintenance and service of the HP POD 20c components IMPORTANT Before installing the HP POD 20c consult your local Authorities for applicable regulations and to review site specific location guidelines If needed obtain any necessary permits Additional considerations for safety and Electrical compliance are ...

Страница 82: ...al and regulatory information see Safety and Compliance Information for Server Storage Power Networking and Rack Products available at the HP website http www hp com support Safety Compliance EnterpriseProducts Turkey RoHS material content declaration Ukraine RoHS material content declaration Warranty information HP ProLiant and X86 Servers and Options http www hp com support ProLiantServers Warra...

Страница 83: ...r off equipment A general term including fittings devices appliances luminaries apparatus machinery and the like used as a part of or in connection with a modular data center Source NEC fuse branch circuit type A fuse of Class CC G H J K L R and T These fuses are able to provide branch circuit protection fuse supplementary type Miscellaneous type and miniature type fuses These fuses are able to pr...

Страница 84: ...ector A manually resettable device designed to open the circuit automatically on a predetermined value of time versus current or voltage within an appliance or other electrical equipment The protector can also be provided manually to open or close the circuit These devices can provide supplementary protection only UL Underwriters Laboratory UPS uninterruptible power system VESDA very early smoke d...

Страница 85: ...oviding documentation that meets your needs To help us improve the documentation send any errors suggestions or comments to Documentation Feedback mailto docsfeedback hp com Include the document title and part number version number or the URL when submitting your feedback ...

Страница 86: ...mponents mechanical 5 contact information 80 contacting HP 80 control cabinet identification 12 control relay module 22 control relay module removing 22 control relay module replacing 22 cooling fan controller 32 cooling fan controller removing 32 cooling fan controller replacing 33 cooling system maintenance 69 customer self repair CSR 80 D differential pressure sensor 60 differential pressure se...

Страница 87: ... sensor replacing 63 I illustrated parts catalog 5 indicators 42 installation considerations 17 L leak detection 70 leak isolation 70 life safety components 5 life safety maintenance 75 light removing 57 light replacing 57 lighting 57 limit switch 23 limit switch removing 23 limit switch replacing 24 M maintenance access control 76 maintenance cooling system 69 manual call point 39 manual call poi...

Страница 88: ...ort 80 telephone numbers 80 temperature sensor 64 65 temperature sensors cold aisle removing 64 temperature sensors cold aisle replacing 65 temperature sensors hot aisle 65 temperature sensors hot aisle removing 66 temperature sensors hot aisle replacing 65 66 thermal air flow performance 78 thermister removing 61 thermister replacing 62 third party components 76 V valves 51 ventilation fan 34 ven...

Отзывы: