For a total thermal load for a system with multiple racks, add the heat outputs for all the racks in
the system.
Table 5 Example Rack Load Calculations
Heat (BTU/hour)
Power Consumption
(Watts)
Weight
Height
(U)
Quantity
Component
(kg)
(lbs)
Maximum
Typical
Maximum
Typical
4848
3696
1420
1084
119.6
264
8
4
Blade element (16
GB CPU)
2225
1788
652
524
56.4
124
8
2
VIO enclosure
854
512
250
150
34
76
4
2
D2700 SAS disk
enclosure (no disks)
1500
850
450
250
25
50
NA
50
SAS disk drives, 10k
rpm (in 2
enclosures)
1536
921
450
270
52
116
4
2
G6 Storage CLIM
392
358
115 (1 line)
105
11.8
26
1
1
Rack-mount system
console, keyboard,
and monitor
96
96
28 (1 line)
28
5.5
12
1
1
Rack-mount
keyboard, and
monitor
137
137
20 (1 line)
20
4.6
10
2
2
Maintenance switch
-
-
-
-
151
333
42
1
Rack
-
-
-
-
18.2
40
1
1
Pair of iPDU cores
1
-
-
-
-
9.1
20
NA
8
iPDU extension bar
11588
8358
3385
2431
487.2
1071
-
-
Total
1
iPDU=Intelligent PDU
56
System Installation Specifications for NS2300 Systems
Содержание Integrity NonStop i NS2300
Страница 5: ...Ukraine RoHS material content declaration 79 Index 80 Contents 5 ...
Страница 9: ...Figure 1 Example NS2300 System Configuration 42U 9 ...
Страница 31: ...Figure 3 Intelligent PDU Connections Without UPS Power Distribution for NS2300 Systems 31 ...
Страница 33: ...Figure 5 Intelligent PDU Connections With Three Phase UPS Power Distribution for NS2300 Systems 33 ...
Страница 35: ...Figure 7 Modular PDU Connections With Single Phase UPS Power Distribution for NS2300 Systems 35 ...
Страница 36: ...Figure 8 Modular PDU Connections With Three Phase UPS 36 System Installation Specifications for NS2300 Systems ...
Страница 38: ...Figure 9 Example of Bottom AC Power Feed Without UPS 38 System Installation Specifications for NS2300 Systems ...
Страница 39: ...Figure 10 Example of Top AC Power Feed Without UPS Power Distribution for NS2300 Systems 39 ...
Страница 41: ...Figure 12 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2300 Systems 41 ...