Once the downstream UPS is in this state, it still might not immediately perceive stable input
power. The downstream UPS is thus compromised until it achieves a lock on stable input power
and is able to recharge its batteries.
Such problems are very difficult to predict. Their occurrence is a function of the output
characteristics of the primary UPS, the input characteristics of the downstream UPS, and the
load characteristics of the other devices deriving power from the upstream UPS. Factors can
include the other types of loads which are driven by the upstream UPS. Some non-linear loads
such as lighting or larger motors are more likely to distort the upstream UPS output than other
electronic equipment.
The occurrence of these problems is unpredictable and has affected NonStop customers. There
is currently no known method to analytically predict the occurrence of such instability. To ensure
correct UPS function, Hewlett Packard Enterprise recommends that you conduct on-site system
testing and that you try to use the supported UPS configurations described in this appendix.
76
UPS and Data Center Power Configurations
Содержание Integrity NonStop i NS2300
Страница 5: ...Ukraine RoHS material content declaration 79 Index 80 Contents 5 ...
Страница 9: ...Figure 1 Example NS2300 System Configuration 42U 9 ...
Страница 31: ...Figure 3 Intelligent PDU Connections Without UPS Power Distribution for NS2300 Systems 31 ...
Страница 33: ...Figure 5 Intelligent PDU Connections With Three Phase UPS Power Distribution for NS2300 Systems 33 ...
Страница 35: ...Figure 7 Modular PDU Connections With Single Phase UPS Power Distribution for NS2300 Systems 35 ...
Страница 36: ...Figure 8 Modular PDU Connections With Three Phase UPS 36 System Installation Specifications for NS2300 Systems ...
Страница 38: ...Figure 9 Example of Bottom AC Power Feed Without UPS 38 System Installation Specifications for NS2300 Systems ...
Страница 39: ...Figure 10 Example of Top AC Power Feed Without UPS Power Distribution for NS2300 Systems 39 ...
Страница 41: ...Figure 12 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2300 Systems 41 ...