NonStop i System With Two Rack-Mounted UPS in Parallel
shows an example of a non-supported configuration in a NonStop i system with the
left PDUs connected to a rack-mounted UPS, and the right PDUs connected to a different
rack-mounted UPS. In this configuration, OSM manages and monitors the rack-mounted UPSs.
Figure 21 NonStop System With Two Rack-Mounted UPS in Parallel
OSM has the capability to monitor both UPSs, but it does not have the logic to initiate the controlled
shutdown of the I/O operations and processors when utility power fails in this configuration.
•
If the utility power is not restored before both rack-mounted UPSs shut down, any data in
the NonStop i system disk drive write cache that has not been transferred to the disk drive
media is lost.
If you want to extend the UPS battery runtime, Hewlett Packard Enterprise recommends adding
the Extended Runtime Modules (ERMs) to the UPS.
74
UPS and Data Center Power Configurations
Содержание Integrity NonStop i NS2300
Страница 5: ...Ukraine RoHS material content declaration 79 Index 80 Contents 5 ...
Страница 9: ...Figure 1 Example NS2300 System Configuration 42U 9 ...
Страница 31: ...Figure 3 Intelligent PDU Connections Without UPS Power Distribution for NS2300 Systems 31 ...
Страница 33: ...Figure 5 Intelligent PDU Connections With Three Phase UPS Power Distribution for NS2300 Systems 33 ...
Страница 35: ...Figure 7 Modular PDU Connections With Single Phase UPS Power Distribution for NS2300 Systems 35 ...
Страница 36: ...Figure 8 Modular PDU Connections With Three Phase UPS 36 System Installation Specifications for NS2300 Systems ...
Страница 38: ...Figure 9 Example of Bottom AC Power Feed Without UPS 38 System Installation Specifications for NS2300 Systems ...
Страница 39: ...Figure 10 Example of Top AC Power Feed Without UPS Power Distribution for NS2300 Systems 39 ...
Страница 41: ...Figure 12 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2300 Systems 41 ...