Maximum Power
Consumption (Watts)
Typical Power
Consumption (Watts)
AC Power Lines per
Enclosure
1
Enclosure Type
190
140
2
Gen9 Storage CLIM
200
130
2
G6 IP or Telco CLIM
203
117
2
Gen8 Networking CLIM 5
copper ports (IP or Telco)
210
123
2
Gen8 Networking CLIM 3
copper/2 optical ports (IP or
Telco)
180
130
Gen9 Networking CLIM, 5
copper ports (IP or Telco)
185
135
Gen9 Networking CLIM, 3
copper/2 optical ports (IP or
Telco)
125
75
2
D2700 SAS disk enclosure
(no disks)
125
75
2
D3700 SAS disk enclosure,
empty
9
5
-
SAS disk drive 10k rpm
7
4
-
SAS disk drive 15k rpm
6
6
-
200GB SAS 2.5” SSD, Gen1
6
6
-
200GB SAS 2.5” SSD, Gen2
6
6
-
400GB SAS 2.5” SSD
115
105
1
Rack-mounted system
console (NSCR212)
28
28
1
Rack-mounted keyboard and
monitor
20
20
1
Maintenance switch (Ethernet)
2
1
One of the plugs for an enclosure must be connected to one of the left-side extension bars and the other one connected
to one of the right-side extension bars. PDUs must be supplied from separate branch circuits.
2
Maintenance switch has only one plug. If a UPS is installed in the rack, the maintenance switch plug must be connected
to the extension bars on the right side of the rack.
48
System Installation Specifications for NS2300 Systems
Содержание Integrity NonStop i NS2300
Страница 5: ...Ukraine RoHS material content declaration 79 Index 80 Contents 5 ...
Страница 9: ...Figure 1 Example NS2300 System Configuration 42U 9 ...
Страница 31: ...Figure 3 Intelligent PDU Connections Without UPS Power Distribution for NS2300 Systems 31 ...
Страница 33: ...Figure 5 Intelligent PDU Connections With Three Phase UPS Power Distribution for NS2300 Systems 33 ...
Страница 35: ...Figure 7 Modular PDU Connections With Single Phase UPS Power Distribution for NS2300 Systems 35 ...
Страница 36: ...Figure 8 Modular PDU Connections With Three Phase UPS 36 System Installation Specifications for NS2300 Systems ...
Страница 38: ...Figure 9 Example of Bottom AC Power Feed Without UPS 38 System Installation Specifications for NS2300 Systems ...
Страница 39: ...Figure 10 Example of Top AC Power Feed Without UPS Power Distribution for NS2300 Systems 39 ...
Страница 41: ...Figure 12 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2300 Systems 41 ...