NonStop i System With Rack-Mounted UPS and Data Center UPS in Parallel
shows an example of a non-supported configuration in a NonStop i system with the
left PDUs connected to the rack-mounted UPS, and the right PDUs connected to the data center
UPS. In this configuration, OSM manages and monitors the rack-mounted UPS. However, OSM
does not manage or monitor the data center UPS.
Figure 20 NonStop i System With Rack-Mounted UPS and Data Center UPS in Parallel
When the utility power fails, OSM detects a
UPS AC Input not Present
event from the
rack-mounted UPS. OSM does not recognize the data center UPS. OSM does not detect that
the data center UPS is running on battery and the UPS battery runtime. OSM does not initiate
the controlled shutdown of the I/O operations and processors.
•
The rack-mounted UPS shuts down before the data center UPS.
•
If the utility power is not restored before the data center UPS shuts down, any data in the
NonStop system disk drive write cache that has not been transferred to the disk drive media
is lost.
72
UPS and Data Center Power Configurations
Содержание Integrity NonStop i NS2300
Страница 5: ...Ukraine RoHS material content declaration 79 Index 80 Contents 5 ...
Страница 9: ...Figure 1 Example NS2300 System Configuration 42U 9 ...
Страница 31: ...Figure 3 Intelligent PDU Connections Without UPS Power Distribution for NS2300 Systems 31 ...
Страница 33: ...Figure 5 Intelligent PDU Connections With Three Phase UPS Power Distribution for NS2300 Systems 33 ...
Страница 35: ...Figure 7 Modular PDU Connections With Single Phase UPS Power Distribution for NS2300 Systems 35 ...
Страница 36: ...Figure 8 Modular PDU Connections With Three Phase UPS 36 System Installation Specifications for NS2300 Systems ...
Страница 38: ...Figure 9 Example of Bottom AC Power Feed Without UPS 38 System Installation Specifications for NS2300 Systems ...
Страница 39: ...Figure 10 Example of Top AC Power Feed Without UPS Power Distribution for NS2300 Systems 39 ...
Страница 41: ...Figure 12 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2300 Systems 41 ...