
NonStop i System With a Rack-Mounted UPS
shows an example of a supported configuration in a NonStop i system with the left
PDUs connected to one or more rack-mounted UPS, and the right PDUs connected directly to
the utility power. The rack-mounted UPS is connected to the utility power.
Figure 16 NonStop System With a Rack-Mounted UPS
When OSM detects that one power rail is running on UPS and the other power rail has lost power,
OSM logs an event indicating the beginning of the configured ride-through time period. OSM
monitors if AC power is restored before the ride-through period ends.
•
If AC Power is restored before the ride-through period ends, the ride-through countdown
terminates and OSM does not take further steps to prepare for an outage.
•
If AC Power is not restored before the ride-through periods ends, OSM broadcasts a
PFAIL_SHOUT
command to all processors (the processor running OSM being the last one
in the queue) to shut down the system ServerNet routers and processors. The
PFAIL_SHOUT
command enables disk writes for data that is in transit through controllers and disks to
complete.
66
UPS and Data Center Power Configurations
Содержание Integrity NonStop i NS2300
Страница 5: ...Ukraine RoHS material content declaration 79 Index 80 Contents 5 ...
Страница 9: ...Figure 1 Example NS2300 System Configuration 42U 9 ...
Страница 31: ...Figure 3 Intelligent PDU Connections Without UPS Power Distribution for NS2300 Systems 31 ...
Страница 33: ...Figure 5 Intelligent PDU Connections With Three Phase UPS Power Distribution for NS2300 Systems 33 ...
Страница 35: ...Figure 7 Modular PDU Connections With Single Phase UPS Power Distribution for NS2300 Systems 35 ...
Страница 36: ...Figure 8 Modular PDU Connections With Three Phase UPS 36 System Installation Specifications for NS2300 Systems ...
Страница 38: ...Figure 9 Example of Bottom AC Power Feed Without UPS 38 System Installation Specifications for NS2300 Systems ...
Страница 39: ...Figure 10 Example of Top AC Power Feed Without UPS Power Distribution for NS2300 Systems 39 ...
Страница 41: ...Figure 12 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2300 Systems 41 ...