Total (BTU/hour)
Unit Heat
(BTU/hour)
Maximum
Unit Heat
(BTU/hour) Typical
Number Installed
Enclosure Type
20.5
20.5
200GB SAS 2.5”
SSD, Gen1
20.5
20.5
200GB SAS 2.5”
SSD, Gen2
20.5
20.5
400GB SAS 2.5” SSD
68
68
Maintenance switch
(Ethernet)
1
392
358
Rack-mount system
console (NSCR212)
96
96
Rack-mount keyboard
and display
1
Maintenance switch has only one plug. If a UPS is installed in the rack, the maintenance switch plug must be connected
to the extension bars on the right side of the rack.
Operating Temperature, Humidity, and Altitude
Maximum Rate of Change
per Hour
Recommended Range
1
Operating Range
1
Specification
50° to 95° F (10° to 35° C)
Temperature (rack-mounted
system console and
maintenance switch)
18° F (10° C) Repetitive
68° to 77° F (20° to 25° C)
36° F (20° C) Nonrepetitive
-
50° to 95° F (10° to 35° C)
Temperature (CLIMs, SAS
disk enclosure, blade
elements)
1.8° F (1° C) Repetitive
5.4° F (3° C) Nonrepetitive
6%, noncondensing
40% to 50%,
noncondensing
20% to 80%,
noncondensing
Humidity
-
-
0 to 10,000 feet (0 to 3,000
meters)
Altitude
2
1
Operating and recommended ranges refer to the ambient air temperature and humidity measured 19.7 in. (50 cm)
from the front of the air intake cooling vents.
2
For each 1000 feet (305 m) increase in altitude above 10,000 feet (up to a maximum of 15,000 feet), subtract 1.5× F
(0.83× C) from the upper limit of the operating and recommended temperature ranges.
Nonoperating Temperature, Humidity, and Altitude
•
Temperature:
-22° to 140° F (-30° to 60° C)
◦
◦
Maximum rate of change: 36° F/hr (20° C/hr)
◦
Reasonable rate of change with noncondensing relative humidity during the transition
from warm to cold
•
Relative humidity: 10% to 85%, noncondensing
•
Altitude: 0 to 40,000 feet (0 to 12,000 meters)
54
System Installation Specifications for NS2300 Systems
Содержание Integrity NonStop i NS2300
Страница 5: ...Ukraine RoHS material content declaration 79 Index 80 Contents 5 ...
Страница 9: ...Figure 1 Example NS2300 System Configuration 42U 9 ...
Страница 31: ...Figure 3 Intelligent PDU Connections Without UPS Power Distribution for NS2300 Systems 31 ...
Страница 33: ...Figure 5 Intelligent PDU Connections With Three Phase UPS Power Distribution for NS2300 Systems 33 ...
Страница 35: ...Figure 7 Modular PDU Connections With Single Phase UPS Power Distribution for NS2300 Systems 35 ...
Страница 36: ...Figure 8 Modular PDU Connections With Three Phase UPS 36 System Installation Specifications for NS2300 Systems ...
Страница 38: ...Figure 9 Example of Bottom AC Power Feed Without UPS 38 System Installation Specifications for NS2300 Systems ...
Страница 39: ...Figure 10 Example of Top AC Power Feed Without UPS Power Distribution for NS2300 Systems 39 ...
Страница 41: ...Figure 12 Example of Bottom AC Power Feed With Single Phase UPS Power Distribution for NS2300 Systems 41 ...