The sensor type, name, PDU ID, PDU name, and PDU location is displayed for each sensor.
3.
Confirm that the serial number on the sensor device matches the number in the sensor table.
Configuring environmental sensors
To configure the sensor name, location, alarms, notifications, and details, open the web interface.
Procedure
1.
Open the Settings page.
2.
View the Threshold section on the Settings page. To configure sensors, click
Threshold
.
3.
To configure the desired sensors, click
Edit
.
4.
In the
Edit Extension
dialog box, enter value of
up critical
,
up warning
,
low warning
, or
low
critical
.
5.
To exit the sensor setup, click
Save
.
6.
Repeat this process for additional sensors.
Configuring door sensors
The door sensor status on the Dashboard page displays as OPEN/CLOSE.
Procedure
1.
Navigate to
Thresholds
>
External Sensors
.
2.
Select the door that you want to receive an alarm, trap, or event notification for, and then enable the alarm.
• When the door is closed and the alarm is enabled for closed state,
165 - binary sensor 1 door
is in CLOSE state
is the trap that is received.
• When the door is open and the alarm is enabled for open state,
165 - The binary sensor 1
door is in OPEN state
is the trap that is received.
Connecting and configuring optional hardware
125
Содержание HPE G2 Series
Страница 16: ...3 Secure the tie wrap 16 Introduction ...
Страница 20: ...20 Introduction ...
Страница 23: ...Installing the PDU 23 ...
Страница 25: ... Outlets facing the back of the rack Installing the PDU 25 ...
Страница 26: ... Outlets facing the front of the rack 26 Installing the PDU ...
Страница 28: ... Two mid height PDUs with outlets facing towards the center of the rack 28 Installing the PDU ...
Страница 29: ... Four half height PDUs with outlets facing towards the center of the rack Installing the PDU 29 ...
Страница 31: ... Half height Installing the PDU 31 ...
Страница 34: ...2 Place the locking tape directly above the unit on the rack PDU mounting bracket 34 Installing the PDU ...
Страница 35: ...Installing the PDU 35 ...
Страница 37: ...2 Install the PDU in the rack frame Installing the PDU 37 ...
Страница 47: ...3 Install the PDU Installing the PDU 47 ...
Страница 49: ...Installing the PDU 49 ...
Страница 64: ...Web menu options Menu Illustration Overview Alarms 64 Remote configuration ...
Страница 65: ...Menu Illustration Help Table Continued Remote configuration 65 ...
Страница 66: ...Menu Illustration Language 66 Remote configuration ...
Страница 67: ...Menu Illustration Logs Remote configuration 67 ...
Страница 68: ...Menu Illustration Settings 68 Remote configuration ...
Страница 84: ...84 Remote configuration ...
Страница 92: ...92 Configuring local access ...
Страница 95: ...LED state Description Green red orange blinking Upgrading Off In USB mode OLED menu structure Local display 95 ...
Страница 99: ...Local display 99 ...
Страница 101: ...Local display 101 ...
Страница 107: ...Local display 107 ...
Страница 120: ...120 Connecting and configuring optional hardware ...
Страница 157: ...2 Pull out the Network Management Module from the PDU 3 Insert the new Network Management Module Appendix 157 ...
Страница 158: ...4 Align the Network Management Module and tighten the captive nuts by turning them clockwise 158 Appendix ...
Страница 160: ...3 Connect the ribbon cable to the replacement Network Management Module and the PDU 160 Appendix ...
Страница 161: ...4 Insert the replacement Network Management Module into the PDU and tighten the two screws Appendix 161 ...