COM0
/
COM1
S
ERIAL
I
NTERFACES
98 / 157
System 6844(RC) - V03.00
hopf
Elektronik GmbH
Nottebohmstr. 41
• D-58511 Lüdenscheid • Tel.: +49 (0)2351 9386-86 • Fax: +49 (0)2351 9386-93 • Internet: http://www.hopf.com • E-Mail: [email protected]
6.3.5 SINEC H1
Below the data string SINEC H1 is described.
String request
The data string SINEC H1 can also send by request. The time of output will be set to "send
only by request" and the string will be requested with the ASCII character
"?"
.
6.3.5.1 Specified Settings
Automatic:
no
Required:
no
Blocked:
no
6.3.5.2 Structure
Character No.
Meaning
Hex-Value
1
STX (start of text)
$02
2
"D" ASCII D
$44
3
":" colon
$3A
4
tens day
$30-33
5
unit day
$30-39
6
"." point
$2E
7
tens month
$30-31
8
unit month
$30-39
9
"." point
$2E
10
tens year
$30-39
11
unit year
$30-39
12
";" semicolon
$3B
13
"T" ASCII T
$54
14
":" colon
$3A
15
day of the week
$31-37
16
";" semicolon
$3B
17
"U" ASCII U
$55
18
":" colon
$3A
19
tens hour
$30-32
20
unit hour
$30-39
21
"." point
$2E
22
tens minute
$30-35
23
unit minutes
$30-39
24
"." point
$2E
25
tens second
$30-36
26
unit second
$30-39
27
";" semicolon
$3B
28
"#" or space
$23 / $20
29
"*" or space
$2A / $20
30
"S" or space
$53 / $20
31
"!" or space
$21 / $20
32
ETX (end of text)
$03