6.3.9 SINEC H1 Extended
Below the data string SINEC H1 Extended is described.
String request
The data string SINEC H1 Extended can also send by request. The time of output will be set
to "send only by request" and the string will be requested with the ASCII character
"?"
.
6.3.9.1 Specified Settings
Automatic:
no
Required:
no
Blocked:
no
6.3.9.2 Structure
Character No.
Meaning
Hex-Value
1
STX (start of text)
$02
2
"D" ASCII D
$44
3
":" colon
$3A
4
tens day
$30-33
5
unit day
$30-39
6
"." point
$2E
7
tens month
$30-31
8
unit month
$30-39
9
"." point
$2E
10
tens year
$30-39
11
unit year
$30-39
12
";" semicolon
$3B
13
"T" ASCII T
$54
14
":" colon
$3A
15
day of the week
$31-37
16
";" semicolon
$3B
17
"U" ASCII U
$55
18
":" colon
$3A
19
tens hour
$30-32
20
unit hour
$30-39
21
"." point
$2E
22
tens minute
$30-35
23
unit minutes
$30-39
24
"." point
$2E
25
tens second
$30-36
26
unit second
$30-39
27
";" semicolon
$3B
28
"#" or " " (space)
$23 / $20
29
"*" or " " (space)
$2A / $20
30
"S", "U" or " " (space)
$53 / $55 / $20
31
"!", "A" or " " (space)
$21 / $41 / $20
32
ETX (end of text)