THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
37
68-0311—02
3140
Cool Cycles Per
Hour - Stage 3
1 to 6 CPH
3
Commercial No
ISU 3010 Temperature Control Options
must be set to
Advanced
to view or adjust
cycle rate.
This ISU is only displayed when ISU 1010
Application is set to
Commercial
and ISU
2070 Cool Stages is set to 3 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour
period measured at a 50% load. For
example, when set to 3 CPH, at a 50% load,
the most the system will cycle is 3 times
per hour (10 minutes on, 10 minutes off).
The system cycles less often when load
conditions are less than or greater than a
50% load.
3140
Cool Cycles Per
Hour - Stage 4
1 to 6 CPH
3
Commercial No
ISU 3010 Temperature Control Options
must be set to
Advanced
to view or adjust
cycle rate.
This ISU is only displayed when ISU 1010
Application is set to
Commercial
and ISU
2070 Cool Stages is set to 4 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour
period measured at a 50% load. For
example, when set to 3 CPH, at a 50% load,
the most the system will cycle is 3 times
per hour (10 minutes on, 10 minutes off).
The system cycles less often when load
conditions are less than or greater than a
50% load.