THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—02
56
8100
Clean Tank / Water
Filter Replacement
Reminder
Off
60 Run Time Days
90 Run Time Days
6 Calendar Months
12 Calendar Months
Off
Both
No
This ISU is only displayed if ISU 8000
Humidifier Type is Steam.
Run Time Days are not shown if ISU 8000
Humidifier Type is set to None.
8100
Humidifier Pad
Replacement
Reminder
Off
60 Run Time Days
90 Run Time Days
6 Calendar Months
12 Calendar Months
Off
Both
No
This ISU is only displayed if ISU 8000
Humidifier Type is Bypass or Fan Powered.
Run Time Days are not shown if ISU 8000
Humidifier Type is set to None.
9000
Dehumidification
Equipment
Residential:
None
A/C with Low Speed Fan
A/C with High Speed Fan
Whole House Dehumidifier
Commercial:
None
A/C with Low Speed Fan
A/C with High Speed Fan
Hot Gas Bypass
Dehumidifier
None
Both
No
See “Dehumidification - Residential”
“Dehumidification - Commercial”
9010
Which Sensor will
be used for
Dehumidification
Control?
Thermostat (Internal)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
(Up to 6 Remote Sensors)
Thermostat
(Internal)
Both
No
Select a sensor to control dehumidification
(thermostat or an optional remote sensor).
If multiple sensors are installed, you can
use a different sensor for humidification
control. See “Dehumidification control”
Note: Humidity sensing cannot be
averaged.
9020
Which Indoor
Humidity Sensor
should be
displayed on the
Home Screen?
Humidification Sensor
Dehumidification Sensor
Humidification
Sensor
Both
No
This ISU is only displayed when separate
humidity sensors are used to control
humidification and dehumidification. Only
one of the sensors can be displayed on the
home screen. Select either the
Humidification Sensor or the
Dehumidification Sensor.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes