THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
33
68-0311—02
3050
Staging Control -
Heat Differential
Stage 3
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type
Comfort
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Comfort
Both
No
ISU 3010 Temperature Control Options
must be set to
Advanced
to view or adjust
this ISU.
This ISU is only displayed for conventional
systems that have 3 heat stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of
heating. For example, if stage 3 is set to 2°
F (1.0° C), the indoor temperature must be
2° F (1.0° C) away from the setpoint before
stage 3 turns on. When set to
Comfort
, the
thermostat will use the stage of heating as
needed to keep the indoor temperature
within 1° F (0.5° C) degree of the setpoint.
3060
Staging Control -
Compressor Heat
Differential Stage 1
Comfort
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Comfort
Both
No
ISU 3010 Temperature Control Options
must be set to
Advanced
to view or adjust
this ISU.
This ISU is only displayed if ISU 2010
Heating Equipment Type is
Geothermal
Radiant Heat
and ISU 2050 Geothermal
Forced Air System is set to
Used for
Heating and Cooling.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of
heating. For example, if stage 1 is set to 2°
F (1.0° C), the indoor temperature must be
2° F (1.0° C) away from the setpoint before
stage 1 turns on. When set to
Comfort
, the
thermostat will use the stage of heating as
needed to keep the indoor temperature
within 1° F (0.5° C) degree of the setpoint.
3060
Staging Control -
Compressor Heat
Differential Stage 2
Comfort
1.0° F to 4.5° F from setpoint (in
0.5° F increments)
Comfort
Both
No
ISU 3010 Temperature Control Options
must be set to
Advanced
to view or adjust
this ISU.
This ISU is only displayed if ISU 2010
Heating Equipment Type is
Air to Air Heat
Pump, Geothermal Heat Pump
or
Geothermal Radiant Heat
and there are 2
compressor stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of
heating. For example, if stage 2 is set to 2°
F (1.0° C), the indoor temperature must be
2° F (1.0° C) away from the setpoint before
stage 2 turns on. When set to
Comfort
, the
thermostat will use the stage of heating as
needed to keep the indoor temperature
within 1° F (0.5° C) degree of the setpoint.