THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—02
52
6100
Water Leak Alert
Dry Contact Setup
Normally Open
Normally Closed
Normally Open Both
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
Choose an option appropriate for the type
of device installed:
Normally Open: The Dry Contact device is
normally open and will close when the
device detects water.
Normally Closed: The Dry Contact device is
normally closed and will open when the
device detects water.
6110
What Terminals are
Wired to the
System Shutdown
Alert Dry Contact?
None
S1
S2
S3
S4
None
Both
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
6120
System Shutdown
Alert Dry Contact
Setup
Normally Open
Normally Closed
Normally Open Both
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
Choose an option appropriate for the type
of device installed:
Normally Open: The Dry Contact device is
normally open and will close when the
device is activated.
Normally Closed: The Dry Contact device is
normally closed and will open when the
device is activated.
6130
What Terminals are
Wired to the
Service Needed
Alert Dry Contact?
None
S1
S2
S3
S4
None
Both
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
6140
Service Needed
Alert Dry Contact
Setup
Normally Open
Normally Closed
Normally Open Both
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
Choose an option appropriate for the type
of device installed:
Normally Open: The Dry Contact device is
normally open and will close when the
device is activated.
Normally Closed: The Dry Contact device is
normally closed and will open when the
device is activated.
6150
What Terminals are
Wired to the Fan
Failure Alert Dry
Contact?
None
S1
S2
S3
S4
None
Both
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes