What Sensors are
WIRED to your
System?
Check box on screen for each:
Indoor Air Temperature
Outdoor Air Temperature
Return Air Temperature
Discharge Air Temperature
None
Both
Yes
Wired Sensors requires an EIM (Equipment
Interface Module). This ISU is only
displayed if one of the S1-S4 terminals is
available.
Click boxes on screen to select which
sensors are wired to the S1-S4 terminals at
the EIM.
The thermostat will not display the
Outdoor
Air Temperature
option at ISU 5000 if a
wireless outdoor air sensor is connected.
The thermostat will not display the
Indoor
Air Temperature
option at ISU 5000 if 6
wireless indoor air sensors are connected.
If you have a wired Indoor Air Temperature
network (1, 4, 9 etc), the thermostat will
allow up to 5 wireless indoor air sensors.
The thermostat will not display the
Return /
Discharge Air Temperature
option at ISU
5000 if there is no fan in the system.
5010
Indoor
Temperature
Sensor Name
[Sensor Name]
Indoor Sensor Both
Yes
Wired Sensors requires an EIM (Equipment
Interface Module).
Enter a name (location) of the Wired Indoor
Air Temperature Sensor.
5020
What Terminals are
Wired to the Indoor
Temperature
Sensor?
None
S1
S2
S3
S4
None
Both
Yes
Wired Sensors requires an EIM (Equipment
Interface Module).
5030
Indoor
Temperature
Sensor Type
10K
20K
10K:
if ISU 1010
Application is
Residential
20K:
if ISU 1010:
Application is
Commercial
Both
Yes
Wired Sensors requires an EIM (Equipment
Interface Module).
Select 10K or 20K based on the sensor
installed. Refer to resistance values below:
C7189U1005 = 10K ohm
C7772 = 20K ohm
TR21 = 20K ohm
TR21-A = 10K ohm (IMPORTANT - the
TR21-A must be used in combination with
a TR21 sensor or another TR21-A sensor
for the thermostat to calculate the correct
indoor temperature reading).
See “Wiring guide — Wired Indoor
Sensors” beginning on page 154 for
information on the sensor type you should
select based on how the sensors are wired.
For example, you would select 20K when
you have two TR21-A (10K) sensors wired
in series.
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes